Installation instructions
1. Unit installation
1).Installation location
Host unit
1
Should be installed in a larger & well-ventilated place.
1
Installation location should ensure unhindered access outlet (inlet & outlet shown as below).
1
Install gutter or set up positions near the outfall, to facilitate the drainage.
1
The installation base or bracket should be steady,
to ensure the smooth operation of running units.
1
Make sure the unit is vertical after installation,
and no incline.
1
Make sure not to install the host unit in the any
conditioner of pollution, corrosive gases, sun
and fallen leaves, etc.
1
Installation location must not next to place of
incendive, easy-explosion and fire .
1
Installation must pay attention to the distance
between the barriers shown in below picture
(pay attention to arrow direction).
1
The air inlet and outlet can connect the
φ
150 air duct for air ventilation, see below pic.
Water tank
1
Water tanks should be placed where ambient temperature is above 0
℃
.
1
Can be installed outdoors or the top of the building (based on the size of water tanks and
the load-bearing capacity of the building and so on).
1
Do not install water tanks in the pollution, corrosive gases place.
2).Unit installation
1
Units base can be installed as cement concrete structures, steel brackets can also be used,
add the shockproof rubber pads , make the base surface flat.
1
Units can be designed based on the working performance.
(See Table of technical performance parameters)
1
Unit should have drain or drainage inlets.
1
Normally required to install in the place where setted cement concrete base.
Above 1000mm
1000mm above the top
Air inlet
Air outlet
Heat pump
Heat pump
Heat pump
Heat pump
Air inlet
Air inlet
Above 1000mm
Ⅷ
.Installation instructions
Water heater
≥
m
m
1
0
0
0
Outside Wall
≥
m
m
1
0
0
0
≥
m
m
1
0
0
0
18