Ⅶ
.
Electric Circuit Wiring Diagram
17
6
Setting about S1 & S2 switch
S2 Switch----Long distance demand
6.1 Second Set Point available when S1 switch has well connected.
At the same time, water temp set point setting decided by ambient temp, Parameter
SET 9 and Parameter SET A. (Both SET 9 & SET A Parameter would be adjusted)
o
Parameter SET 9 (maximum setting range 45~60 C)
o
Parameter SET A (minimum setting range 20~40 C)
o
A. When ambient temp < 5 C, set point temp refer to the data of Parameter SET 9
o
B. When ambient temp >15 C, set point temp refer to the data of Parameter SET A
o
o
C. When 5 C
≤
ambient temp
≤
15 C, Set point temp = Data of Parameter SET 9-
(Data of parameter SET 9- data of parameter of SET A)/(15-5)*(Ambient temp -5 )
For example, when ambient temp is 18 deg c, Parameter SET 9 data is 50 deg c,
Parameter SET A data is 20 deg c.Then set point temp =50-(50-20)/(15-5)*(18-5)
S1 Switch---Second Set Point
6.2 When S1 disconnected, set point temp control by LCD controller. (Refer to the
setting of Parameter 40 (default setting 50 deg c).
6.3 Heat pump will turn on when S2 switch has well connected.However, S2 well
connected, and suddenly press the off button on the LCD controller.Heat pump
will stop for 3 minutes. After 3 minutes heat pump continue to turn on if S2 Still
has been connected.
6.4 The timer function is out of validity when S2 switch is connected.
6.5 Heat pump turns off when S2 switch is disconnected. Meanwhile, need to use
LCD controller to switch on/off the heat pump.
2
2
2
2
2
2
4
5
AC-N
4-
way
V
alve
T
ransformer
CN7
OUT3
OUT2
OUT4 OUT5 OUT6 OUT7 OUT8 OUT9
NO
COM
T5
T4
T3
T6
T2
T1
SEN5
SEN7
SEN6
SEN8
SEN4
SEN3
SEN2
SEN1
+12V CND B- A+ PORT5 PORT4 PORT3 PORT2 PORT1 SEN9
High
Pressure
Switch
Low
Pressure
Switch
Wire
controller
FM
Water
flow
WIRING DIAGRAM
PORT6 PORT7
1 2
From POWER SOURCE
CM
R
C
S
Compressor
L N
Electronic
Expansion Valve
Water pump
PM
Ⅵ
.Operation introduction
Water heater
S1
3 4 5
S2
T1
T2
T3
T4
T5
T6
S1 Second set point
S2 Long distance demand for heating
Water inlet temp sensor
Water outlet temp sensor
Exhaust temp sensor
Coil temp sensor
Ambient temp sensor
Air Circulation Temp Sensor
To Ac
contactor
of E-heater