Option

01

02

03

04

05

06

07

08

09

10

12

13

14

15

16

17

19

18

20

21

Description

Compressor Stages

Heating Stages. 

Fan Operation. 

Compressor Minimum Off Time (minutes).

Gas Minimum Off Time (minutes).

Minimum Run Time (minutes).

On-Off Temperature Differential

Smart Recovery.

Vacant Heating Setpoint.

Vacant Cooling Setpoint.

Night Level LCD Backlight

Airflow Control On or Off

Enable Selecting Manual Airflow Control.

Maximum Upstairs Airflow in Heating.

Maximum Downstairs Airflow in Heating.

Maximum Upstairs Airflow in Cooling.

Maximum Downstairs Airflow in Cooling.

Maximum Temperature Difference Between
Upstairs and Downstairs.

Factory Restore

0  Cooling On 1  above setpoint, Off at setpoint.  Heating On1  below setpoint, Off at setpoint.

o

o

1  Cooling On 1  above setpoint, Off .5  below setpoint.  Heating On1  below setpoint, Off .5  above  setpoint.

o

o

o

o

2  Cooling On 1  above setpoint, Off 1  below setpoint.  Heating On1  below setpoint, Off 1  above  setpoint.

o

o

o

o

Display

Cpr

+ Heat

+ Cool

BL

AFC

UFC

HAF+Heat

HAF+Heat

CAF+Cool

CAF+Cool

diF

Fr

Htg

Fan

Cot

HOt

O O o

S r

V A C 

V A C 

Range

0 or 1

0 or 1

GA(Up) or EL(Down)

0 to 9

0 to 9

0, 1 or 2

0n(Up) or Off(Down)

44 to 75

74 to 95

On(Up) or Off(Down)

On(Up) or Off(Down)

On(Up) or Off(Down)

100 to 160%

100 to 160%

100 to 160%

100 to 160%

0 to 10

No(Next) or Yes(Enter)

Default

1

1

GA

2

0

1

Off

65

80

On

On

Off

150%

150%

140%

140%

2

NA

 + Night

INSTALLER OPTIONS

r n t

0 to 9

2

11

Calibrate Downstairs Sensor

C A L

+/- 5

0

Airflow Update Time

A F t

1 to 20 minutes

2

ACCESSING INSTALLER OPTIONS

To access the Installer Options, 

 and 

 the hidden Enter 

key for 7 seconds until the first Option appears on the screen.

TOUCH

HOLD

Inside

Tu

Day

Upstairs

Auto

Downstairs

Airflow %

COOL

Schedule

AUTO

FAN

MENU

MODE

Cool

Set To

SYSTEM

AM

TOUCH

HOLD

 and 

 this key for 7 seconds

to access the Installer Options.

Touch the

 keys to 

set 0 or 1 stage.

Touch 

 to display the 

next option.  After about 20 
seconds, the installer options 
will time out and return to 
normal thermostat operation. 

 UP/DOWN

NEXT

Option

NEXT

ENTER

01  Setting the Compressor Stages

This option is used to set the number of cooling stages.

Option

NEXT

ENTER

Touch the

 keys to 

set 0 or 1 stage.

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation, or touch 
the hidden 

 key to return 

to the previous option.

 UP/DOWN

NEXT

 ENTER

BACK

This option is used to set the number of heating stages.

Option

NEXT

ENTER

Touch the 

 key to select 

“EL” for electric operation 
where the thermostat activates 
the indoor fan (G terminal) 
during heating calls or 

 

key to select GA for gas 
operation where the equipment 
plenum sensor activates the 
indoor fan in heating calls. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation.

UP

DOWN

NEXT

 ENTER

5

22

Calibrate Upstairs Sensor.

C A L

+/- 5

0

Factory Default: 1 Stage. Range: 0 or 1

02  Setting the Heating Stages

Factory Default: 1 Stage. Range: 0 or 1

03  Setting the Fan Operation in Heating

Factory Default: Gas.  Range: GA or EL

The hidden BACK key can be 
used to return to previous options.

Содержание Comfort 365 C365T11

Страница 1: ...ing only Cooling only Automatic Heating or Cooling Maximum upstairs and downstairs heating and cooling airflow limits are set during installation Option used when bedrooms are located upstairs C365 uses the upstairs temperature sensor to control heating and cooling calls and directs more airflow upstairs One Model TS5 10 or two Model TS5 20 upstairs temperature sensors can be used Round or rectang...

Страница 2: ...the battery cover downward and install the two AA batteries as shown R C W EQUIPMENT Y G Upstairs Sensor COM COM CLS CLS OPN OPN Upstairs Downstairs Install an R80CT damper in the duct supplying air to the upstairs and wire the terminals to the corresponding terminals on the C365T Install a second R80CT damper in the duct supplying air to the downstairs and wire it to the C365T Each damper uses 2 ...

Страница 3: ... upstairs and downstairs dampers There are separate terminals for the upstairs and the downstairs dampers Multiple dampers can be used to construct the upstairs or downstairs zones Daisy chain terminals COM to COM OPN to OPN and CLS to CLS Use 2 conductor 18 or 20 gage thermostat cable to wire from the C365 Thermostat to the upstairs temperature sensor C365 Terminal C365 Terminal C365 Terminal R C...

Страница 4: ... and Day NEXT ENTER AM Touch the UP DOWN keys to change the HOUR Touch NEXT to save the hour and go to change the minute CHANGE THE HOUR Touch the UP DOWN keys to change the MINUTE Touch NEXT to save the minute and go to change the day of the week CHANGE THE MINUTE Touch the UP DOWN keys to change the DAY OF THE WEEK Touch ENTER to save the day fo the week and return to thermostat operation CHANGE...

Страница 5: ... L 5 0 Airflow Update Time A F t 1 to 20 minutes 2 ACCESSING INSTALLER OPTIONS To access the Installer Options and the hidden Enter key for 7 seconds until the first Option appears on the screen TOUCH HOLD Inside Tu Day Upstairs Auto Downstairs Airflow COOL Schedule AUTO FAN MENU MODE Cool Set To SYSTEM AM TOUCH HOLD and this key for 7 seconds to access the Installer Options Touch the keys to set ...

Страница 6: ...e previous option UP DOWN NEXT ENTER BACK Option NEXT ENTER Touch the keys to select the cooling temperature when the space is vacant Touch to display the next option or to save the option and return to normal thermostat operation or touch the hidden key to return to the previous option UP DOWN NEXT ENTER BACK Option NEXT ENTER Cool Vacant Vacant Touch the keys to change the downstairs Inside temp...

Страница 7: ...ion NEXT ENTER Cool Touch the keys to select the maximum allowable downstairs airflow in heating Touch to display the next option or to save the option and return to normal thermostat operation or touch the hidden key to return to the previous option UP DOWN NEXT ENTER BACK Downstairs Airflow Option NEXT ENTER Heat Touch the keys to select the maximum allowable downstairs airflow in cooling Touch ...

Страница 8: ...stairs Airflow in Heating Upstairs Downstairs Airflow NEXT ENTER Heat To determine the maximum allowable downstairs airflow touch the key until the airflow is too great and causes noise or annoyance Increase the airflow using the key until it is acceptable This is the maximum allowable downstairs airflow in heating Record the airflow value DOWN UP Maximum Allowable Downstairs Airflow in Heating 05...

Отзывы: