AB1…SE instructions 12 of 12
Form 140516
13.3
E
LECTRONIC
C
ONFIGURATION
AB1…SE5
I
NPUT SIGNAL
4-20
M
A
DIP SWITCH POSITION
D
IP
S
WITCH
D
IP
S
WITCH
O
N
LEFT
O
FF
D
IP
S
WITCH
O
N
RIGHT
O
N
1
Clockwise Rotation
(from Power End side)
Counter-Clockwise Rotation
(from Power End side)
2
Low Resolution 125 steps
High Resolution 200 steps
3
4
Please refer to the below reported scheme
5
Input Signal 0-10 V d.c.
Input Signal 4 – 20 mA
DS-6 MUST be turned ON
6
Impedance at 4400 Ohm
(only for Input Signal 0-10V).
Always turned ON with Input
Signal 4-20 mA
Impedance at 250 Ohm
(only for Input Signal 0-10V).
** For special setting please look here below:
3
•
4
OFF
•
ON
STANDARD setting, Input and Output signal always aligned. For
example 2V input e 2V output.
3
•
4
OFF
•
ON
REVERSE OUTPUT (only for counter-clockwise rotation). For
example 2V Input signal and 8V Output Signal.
3
•
4
OFF
•
ON
DS-3 turned ON and DS-4 turned OFF. Actuator rotates for 90°
with Mid-Low Input Signal. For example 4-12 mA with rotation of
90°.
3
•
4
OFF
•
ON
DS-3 turned OFF and DS-4 turned ON. Actuator rotates for 90°
with Mid-High Input Signal. For example 12-20 mA with rotation of
90°.
This manual can be amended without any obligation of notice