AB1…SE instructions 2 of 12
Form 140516
1 GENERAL
FEATURES
Electronic rotary gear motors of series AB1...SE have been newly conceived and specially
designed to be installed on residential and industrial combustion systems.
They are particularly suitable for control and regulation of modulating disc valves, butterfly
valves, dampers and other fluid regulation systems requiring control of position angle
within 90°. Electronic rotary gear motors are unipolar and bidirectional with high static and
maintaing torque. Analogic input signal according to current [4 ÷ 20 mA] or voltage change
[0 ÷ 10 Vdc].
W
ARNING
Installation, wiring, adjustment and maintenance of gear motors must be carried out
exclusively by skilled and authorized service technicians. Non-proper installation,
adjustment, modifications, use and maintenance may cause injuries to the staff or material
damages. It is therefore necessary to respect strictly the following instructions and local
prescriptions for the installation of electronic devices.
2 TECHNICAL
DATA
Body and cover
die-cast aluminium
Nominal torque
3 ÷ 5 Nm
Maintaining torque
2,5 ÷ 3 Nm
Rotation time
15 ÷ 60 seconds for 90° at 50 Hz
Output shaft
10 mm diameter
Rotation angle
standard 90°
Installation
in any position
Fastening bore
DIN ISO 5211 – F05 and F07
Ambient temperature
- 10° ÷ + 60° C
Weight
1.7 Kg
Standard supply voltage
24 Vac / 50 - 60 Hz
On request
with trafo 115V
∼
up to 24 V
∼
with trafo 230V
∼
up to 24 V
∼
Standard input signal
4 ÷ 20 mA or
On request
0 ÷ 10 Vdc
Nominal load
4 -7 VA
Impedance input signal
250 ohm / 4 kohm
Rating of electronic contacts of
endswitches and auxiliary switches
0,5 A / 48 Vdc and Vac
Enclosure
IP 54 according to IEC 529
Available potentiometer
1000 ohm
Duty cycle
continuous 100%
Cable entry
2 x Pg 13.5
Manual/Automatic operation and service switch "Open/Stop/Closed"