background image

 

AB1…SE instructions                                                                                                                                    2 of  12 
Form 140516 

 

 
   

1 GENERAL 

FEATURES 

 

Electronic rotary gear motors of series AB1...SE have been newly conceived and specially 
designed to be installed on residential and industrial combustion systems. 
They are particularly suitable for control and regulation of modulating disc valves, butterfly 
valves, dampers and other fluid regulation systems requiring control of position angle 
within 90°. Electronic rotary gear motors are unipolar and bidirectional with high static and 
maintaing torque. Analogic input signal according to current [4 ÷ 20 mA] or voltage change 
[0 ÷ 10 Vdc]. 
 

 

 

W

ARNING

 

Installation, wiring, adjustment and maintenance of gear motors must be carried out 
exclusively by skilled and authorized service technicians. Non-proper installation, 
adjustment, modifications, use and maintenance may cause injuries to the staff or material 
damages. It is therefore necessary to respect strictly the following instructions and local 
prescriptions for the installation of electronic devices. 

 
 

 

2 TECHNICAL 

DATA 

 

Body and cover                                

die-cast aluminium 

Nominal torque                                 

3 ÷  5  Nm 

Maintaining torque                             

2,5 ÷ 3  Nm 

Rotation time                                   

15 ÷ 60 seconds for 90° at 50 Hz 

Output shaft                                    

10 mm diameter 

Rotation angle                  

standard 90° 

Installation                                       

in any position 

Fastening bore                                 

DIN ISO 5211 – F05 and F07 

Ambient temperature                        

- 10° ÷ + 60° C 

Weight                                             

1.7 Kg 

Standard supply voltage                  

24 Vac / 50 - 60 Hz 

On request 

with trafo 115V

 up to 24 V

 

 

with trafo 230V

 up to 24 V

 

Standard input signal 

4 ÷ 20 mA  or 

On request 

0 ÷ 10 Vdc 

Nominal load                                    

4 -7 VA 

Impedance input signal 

250 ohm / 4 kohm 

Rating of electronic contacts of 
endswitches and auxiliary switches   

0,5 A / 48 Vdc and Vac 

Enclosure                          

IP 54 according to IEC 529 

Available potentiometer 

1000 ohm 

Duty cycle                                        

continuous 100% 

Cable entry                                   

2 x Pg 13.5 

Manual/Automatic operation and service switch "Open/Stop/Closed" 

Содержание AB1 SE Series

Страница 1: ...AL OF POT B POSITION 5 6 AUXILIARY MICROSWITCHES 5 7 FEEDBACK POTENTIOMETER S 6 8 CONTROL STATION 6 9 ADJUSTMENTS 7 9 1 ENDSWITCHES 7 9 2 ELECTRONIC BOARD ONLY ON EMERGENCY 8 10 OPERATING 8 11 MAINTEN...

Страница 2: ...enance may cause injuries to the staff or material damages It is therefore necessary to respect strictly the following instructions and local prescriptions for the installation of electronic devices 2...

Страница 3: ...se 3 closes by decreasing of the input signal between terminals 2 3 counter clockwise 4 opens by increasing of the input signal between terminals 2 3 3 5 AB1 SE gear motor must be free to be stopped b...

Страница 4: ...e their section must be ranging between 1 and 1 5 mm2 Connection piping recommended H07V U G1 5 mm2 4 7 Connection wiring diagrams show AB1 SE gear motor at end position closed 0 4 8 Auxiliary microsw...

Страница 5: ...losed contact of the auxiliary microswitch S3 Terminal 23 common contact of the auxiliary microswitch S4 Terminal 24 normally open contact of the auxiliary microswitch S4 Terminal 25 normally closed c...

Страница 6: ...set on AUTOMATIC operation When the gear motor is powered a green led light between the two push bottons flashes four times repetadly 8 3 To select MANUAL operation push both keys simultaneously for a...

Страница 7: ...d inside 9 1 4 Use the key from the right side introducing the pin into one of the holes on the sides oftheblue cam of the cam involved and lever it to desired position 9 1 5 If the blue cam is in a b...

Страница 8: ...2 9 Calibrate the S2 cam nearly for starting point of microswitch 9 2 10 Adjust the control device on 4 mA or 0 Vdc setting the motor at 0 on return 10 OPERATING After installation and adjustment of t...

Страница 9: ...regoing chapters 13 ELECTRONIC CONFIGURATION The digital electronic board mounted on AR2 gear actuator enables to set various features options like rotation direction resolution type of input control...

Страница 10: ...always aligned 5 Input Signal 0 10 V d c Input Signal 4 20 mA DS 6 MUST be turned ON 6 DS 6 MUST be turned OFF N A For other setting please look here below 3 4 OFF ON STANDARD setting Input and Output...

Страница 11: ...Low Resolution 125 steps High Resolution 200 steps 3 4 Please refer to the below reported scheme 5 N A Input Signal 0 10 V 6 N A DS 6 MUST be turned ON For special setting please look here below 3 4...

Страница 12: ...0V Always turned ON with Input Signal 4 20 mA Impedance at 250 Ohm only for Input Signal 0 10V For special setting please look here below 3 4 OFF ON STANDARD setting Input and Output signal always ali...

Отзывы: