Error Code
Name
Description
Solution suggestion
1
IPM over-current
There is something wrong with IPM
module
Replace inverter module
2
Compressor
synchronization is
abnormal
Compressor failure
Replace compressor
4
reserved
--
--
8
Compressor
output
phase absence
Compressor wiring is disconnected
or the connection is poor
Check compressor input
wiring
16
Low DC bus voltage
Input voltage is too low , PFC module
failure,
Check the input voltage,
replace inverter module
32
High DC bus voltage Input voltage is too high, PFC
Module failure
Replace inverter module
64
Radiator over
temperature
Fan motor failure, air duct blockage
Check fan motor, air duct
128
Radiator temperature
failure
Radiator sensor is damaged
Replace inverter module
257
Communication
failure
Inverter module doesn’t receive
message from main controller
Check the connection
between main controller
and inverter module
258
AC Input phase
absence
Input phase is absent (Three phase
module is effective)
Check input circuit
260
AC Input over-current Input three phase imbalance (three
phase module is effective)
Check input three-phase
voltage
264
Low voltage of AC
Input
Input voltage is too low
Check input voltage
272
High pressure
protection
Reserved