Installation & Operation Manual
ECON actuator Fig. 7917EX, type ELSA50 – 260
www.eriks.com
Rev. 0 – April 10
th
, 2019
27
7. Actuator Options
Valve
’s
operating
direction
Handwheel direction
Adjust the tag and position
indicator.
Direct mount per
original factory setting.
Direct mount per
original factory setting.
Fail clockwise (CW) rotation
When energized, the driven valve
rotates CCW (viewed from the top of
the actuator). Meanwhile, the springs
are compressed. On loss of power,
the spring returns (unloaded) and the
driven valve rotates CW.
Fail counter-clockwise (CCW) rotation
When energized, the driven valve rotates
CW (viewed from the top of the
actuator). Meanwhile, the springs are
compressed. On loss of power, the
spring returns (unloaded) and the driven
valve rotates CCW.