Installation & Operation Manual

 

 

 

ECON actuator Fig. 7917EX, type ELSA50 – 260 

  

www.eriks.com

 

Rev. 0 – April 10

th

, 2019 

24

 

5.7  Troubleshooting of modulating controller

 

 

 In case LD3 does not light or any of LD 5 to LD9 lights when the actuator is 
motorized, please refer to steps below for basic troubleshooting.  

 

Status of 

LEDs

 

Possible problems

 

Solution

 

LD3 does 
not light up

 

a.  No power supplied. 
b.  Incorrect connection of the lines 

#8, #9 of the potentiometer 

c.  Modulating controller failed. 

a.  Check the power supply as well as the 

wires connected to terminals #4 & #5, 
please refer to section 5. 

b.  Verify the actuator is wired properly as per 

wiring diagram.  

c.  Send back to the factory for inspection.

 

LD5 lights 
up

 

a.  An incorrect signal type 

inputted. 
For example, preset with 2-10 V 
input but input 4-20 mA. 
Or preset with 4 - 20 mA input 
but input 2 - 10V signal.  In this 
case, the actuator still works in 
2 - 7V.  When the signal is over 
7.2 V the LD5 lights. 

b.  Input a voltage exceeding the 

rated.  For example, preset with 
2-10 V input but input 13.5V.

 

Verify if the switch 1 is set in accordance with 
the type of input signal.  

Please refer to section 5.3. 

LD 6 lights 
up

 

Motor thermal protector started.

 

a.  The duty cycle exceeded the rated. 
b.  The contact of motor thermal protector 

(MOT) disconnected.

 

LD7 lights 
up

 

a.  Signal output short circuit. 
b.  The input signal type 2-10 V 

with reversed polarity.  .

 

a.  Verify if the signal output with reversed 

polarity. The negative pole should be 
connected to terminal #11 and the positive 
pole should be connected to terminal 12 

b.  Verify if the signal input with reversed 

polarity when applying 2-10V, the negative 
pole should be connected to terminal #6 
and the positive pole should be connected 
to terminal #7.

 

LD8 lights 
up

 

Motor over-current. 

a.  Duty cycle exceeded the rated. 

Please refer to 3.6  and reduce the duty rating. 

b.  Check the load. 
     Check if the motor rotor is locked (For 

example: Valve is stuck by foreign objects).

 

LD9 lights 
up

 

Local setting mode - Setting 
position for open & close.

 

After completing setting, press “SET” button to 
quit.

 

 

Содержание ELSA130

Страница 1: ...n Manual ECON actuator Fig 7917EX type ELSA50 260 www eriks com Rev 0 April 10th 2019 ECON SPRING RETURN ELECTRIC ACTUATOR Fig 7917EX type ELSA50 260 Installation and Operation Manual for actuator typ...

Страница 2: ...ator Selection 8 3 5 Sizing 9 3 6 Duty Cycle IEC 9 3 7 Flame path Joint 9 4 Mounting And Setup 11 4 1 Handwheel Installation 11 4 2 Valve Mounting Instructions 11 4 3 Wiring Instructions 13 4 4 Actuat...

Страница 3: ...rce on the handwheel for operating as this can damage the actuator or valve 1 2 1 General The spring return actuator is shipped in spring return position spring unloaded Standard actuators will be sup...

Страница 4: ...ase refer to section 1 2 3 To avoid functional failure caused by a static load do not touch any components on the PCB with metal tools or bare hands Use proper cable glands in order to seal the condui...

Страница 5: ...ure of 105 C 221 F Working Conditions ATEX IECEx Atmospheric pressure 80 110 kPa Ambient temperature 30 C to 70 C 22 F to 158 F Relative humidity Not more than 95 25 C 77 F The actuator can operate no...

Страница 6: ...ed in a dry area with a relative humidity of less than 90 20 5 C and at a temperature between 20 C to 40 C 4 F to 104 F The product shall be stored with suitable protection from corrosive substances w...

Страница 7: ...ring stroke to reduce the water hammer effects in pipes A clutch less manual override is provided for manual positioning of the controlled device Actuators without a manual override can be ordered as...

Страница 8: ...erial Number Date of manufacture ATEX and IECEx markings ATEX and IECEx certificate No Please make sure the explosion proof specification for the product is in consistence with nameplate and instructi...

Страница 9: ...ls 3 4 Actuator Selection Model Mounting Flange Shaft A Depth of Shaft B ISO 5211 mm inch mm inch ELSA50 F07 17 0 669 30 1 181 ELSA130 F10 22 0 866 41 1 614 ELSA200 F12 27 1 063 45 1 772 ELSA260 F12 2...

Страница 10: ...e running time and resting time It is calculated as below Duty Cycle x 100 Rest Time s If the motor running time is 10 s the spring return time is 5 s and the duty cycle is 50 the rest off time shall...

Страница 11: ...as it will damage the closing surfaces Cover Installation Please ensure that the O ring seal is in good condition prior to cover installation Slowly re install the cover while being careful not to pi...

Страница 12: ...9 11 4 Mounting And Setup 4 1 Handwheel Installation a Slide the fixing screw through the washers and handwheel and secure them to the override shaft as shown in the figure below Turn off power when i...

Страница 13: ...it ensure that they are properly secured together by fastening all fasteners by using corrects tools f Remove the conduit entry plug to relieve the pressure inside the actuator for the ease of the top...

Страница 14: ...lugs to reach the explosion proof function Please refer to section 1 2 2 4 4 Actuator Set up If the actuator is equipped with a manual override rotate the handwheel to return the actuator to its fully...

Страница 15: ...e End Stop using a 10mm hex wrench to adjust the end position c Turn the buffer or End Stop in order to adjust the fully closed stop point ELSA50 One turn 2 3 degrees ELSA130 to ELSA260 One turn 1 4 d...

Страница 16: ...g angle turn the cam clockwise To decrease the opening angle turn the cam counter clockwise ELSA50 ELSA130 up to ELSA260 d After adjusting the cam apply power to drive the actuator to the fully open p...

Страница 17: ...nt ELSA50 One turn 2 3 degrees ELSA130 to ELSA260 One turn 1 4 degrees d Once completed tighten the hex nut replace cover and tighten the bolts If the buffer or End Stop is adjusted TC2 must be reset...

Страница 18: ...losed position If it is in correct position turn the power supply off and lock the cap bolt of cam TC1 If it is not in the correct position repeat step C until the correct position is reached f If aux...

Страница 19: ...y closed stop point Once the spring mechanism has been released when power outage the actuator will not drive under power again until it has reached its fail stop position and TC2 trips TC1 OPEN Clock...

Страница 20: ...ease follow the steps below if an adjustment of these settings are required Please restart the actuator after adjusting 1 2 3 4 5 6 7 8 Factory Setting ON OFF OFF ON OFF OFF OFF ON 4 20 mA input ON OF...

Страница 21: ...tch 6 is used to set the corresponding relationship between value of signal input and operation direction of actuator When S6 is set to ON The program defines 20 mA or 5 V or 10 V as a command for ful...

Страница 22: ...When S6 is set to OFF The program defines 20 mA 5 V 10 V as a command for fully open positioning The line graph below shows the signal level and the corresponding position of the actuator When a high...

Страница 23: ...ch Setting SW2 Original factory setting is 3 When switched to 1 The Highest Sensitivity is activated and the 0 90 degree travel is divided up to around 80 movements When switched to 0 The Lowest Sensi...

Страница 24: ...fully open setting is completed Fully CLOSED setting a Press and hold the DOWN switch to operate the actuator to close until it has reached fully closed position and LD1 lights Then put in a signal of...

Страница 25: ...LD5 lights b Input a voltage exceeding the rated For example preset with 2 10 V input but input 13 5V Verify if the switch 1 is set in accordance with the type of input signal Please refer to section...

Страница 26: ...rates too frequently and exceeded duty cycle rating b A torque overload caused by the valve c Supply voltage was too high or too low out the tolerance of deviation d Wrong power supply a Adjust the sy...

Страница 27: ...but not modulating Possible problems Solution The signal input with a reversed polarity it means a signal failure Verify if the negative pole of signal input connected to terminal 6 and the positive...

Страница 28: ...riginal factory setting Fail clockwise CW rotation When energized the driven valve rotates CCW viewed from the top of the actuator Meanwhile the springs are compressed On loss of power the spring retu...

Страница 29: ...ft Rotate the indicator 90 degrees and lock the screws then re install the indicator scale Figure 2 The tag of CLOSE direction with an arrow pointing on the handwheel is printed on both of the sides A...

Страница 30: ...260 www eriks com Rev 0 April 10th 2019 29 If you have questions about this product Please contact the nearest ECON distributor You can find them on www eriks com ERIKS Flow Control Cypresbaan 63 290...

Отзывы: