Installation & Operation Manual Proven Quality since 1892
ECON actuator Fig. 7907, type ELA80 – 3000
Rev.13 - January 7, 2019
26
4.12.2 Features
The actuator unit can be operated in Local or Remote mode, also during power failure.
The DIP switch settings and functions can be found in the table in paragraph 4.
NORMAL MODE (on AC POWER): Battery LED blinks 1.5 seconds ON and 0.5 seconds OFF
BATTERY MODE (on BATTERY POWER) : Battery LED blinks 0.25 seconds ON and 1.75
seconds OFF
4.12.3 Specification
Items
Condition
Electric Power Supply
1 Phase – AC 115 V / 230 V 50/60Hz
Internal Voltage
Control Voltage : DC 24 V / 30 V
Voltage for Space Heater : AC 115/230 V
Power Consumption
40 VA
Temperature / Humidity
-20 ~ 70°C / 60 % RX, MAX.
Actuator functions by DIP
switch settings
DIP Switch setting
DIP switch 1
OFF
INCHING
ON
HOLD
DIP switch 2
OFF
Fault Contact Normal Open
ON
Fault Contact Normal Close
Power Fail action
DIP switch 3
DIP switch 4
FUNCTION
OFF
OFF
STOP
OFF
ON
CLOSE
ON
OFF
OPEN
ON
ON
NO POWER FAIL ACTION