J) Deadband Dial
The deadband adjusts the limits of the valve’s
deviation between an actual position and a target
position. The dead band is set to 0.12mA DC
max.
Deadband indicates the extent of the reaction on
the input signal.
Low deadband setting may cause the actuator
to hunt or to unnecessarily respond to a
fluctuating input signal. If so, the deadband must
be increased.
Turning the Deadband Dial in clockwise direction
will increase the resolution (Range 0.0625mA to
1mA).
4.11
AC/DC Multi-Board (Optional)
A) Power Open-Close Terminal block
1
Power 24V AC/DC (DC + signal block)
2
None
3
None
4
Open signal
5
Close signal
6
Power 24V AC/DC (DC – signal block)
B) Power Input Switch
Dial
0
1
2
3
mA DC
0.0625
0.125
0.1875
0.25
Dial
4
5
6
7
mA DC
0.3125
0.375
0.4375
0.5
Dial
8
9
A
B
mA DC
0.5625
0.625
0.6875
0.75
Dial
C
D
E
F
mA DC
0.8125
0.875
0.9375
1
Deadband
Dial