7

Scan of the Maximum and Minimum Value

1.  Press the HOLD key. 

• Measured values are "frozen" and the value at the time the key is    
  pressed is displayed. 

2.  Press the HOLD key twice. 

• Minimum value, smallest value since switching on the device, is  
 displayed. 

3.  Press the HOLD key 3 times. 

• Maximum value, the highest value since the device was switched on,  
  is displayed. 

4.  Press the HOLD key 4 times. 

• ecom-UNO is in measuring mode again. 

5.  Hold the HOLD key.

• Minimum and maximum values are deleted.

Содержание UNO

Страница 1: ...OPERATION MANUAL English Status Nov 2020 Version ecom UNO 200 hPa ...

Страница 2: ...tive and differen tial pressure of gases It is particularly suitable for work on heating venti lation and air conditioning systems The measuring range covers pressures from 200 hPa to 200 hPa Scope of Delivery ecom UNO 200 hPa 2x 1 5 V AA Batteries Protective bag option ...

Страница 3: ... in moist rooms or at sub zero temperatures Damage of the Sensors Substances containing solvents damage the device s sensors Avoid contact with substances containing solvents WARNING Hazard of Injury Improper work on incinerators can cause injuries Work on incinerators may only be done by qualified specialists WARNING Magnetic Field The magnetic field can cause pacemakers to malfunction in their i...

Страница 4: ...4 Device Description 1 Connection Overpressure 4 Battery Capacity 7 HOLD Key 2 Connection Depression 5 Cursor 8 Setting Key 3 Display 6 Pressure Units 9 ON OFF 6 7 8 9 5 4 3 1 2 ...

Страница 5: ...be attached to most metal surfaces WARNING Magnetic Field The magnetic field can cause pacemakers to malfunction in their impair Operation of the ecom UNO by persons with pacemakers is prohibited NOTICE ecom UNO carries out a segment test when switched on It starts in the lower measuring range and is ready to measure after 3 s Segment test ready to measure ...

Страница 6: ... hPa mbar to 0 1 hPa mbar Range Overload If the measuring range of 200 hPa to 200 hPa is exceeded 4 lines appear on the display Display Damping The display damping can be set from 1 weak damping to 9 strong damping see setup Zero Point Correction The zero point correction is used to compensate the zero point drift after switching on the instrument see setup Set Zero Point Press the setting key Uni...

Страница 7: ...isplayed 2 Press the HOLD key twice Minimum value smallest value since switching on the device is displayed 3 Press the HOLD key 3 times Maximum value the highest value since the device was switched on is displayed 4 Press the HOLD key 4 times ecom UNO is in measuring mode again 5 Hold the HOLD key Minimum and maximum values are deleted ...

Страница 8: ... on the unit The following functions can be set Select a function with the ON OFF key Setting is made with the HOLD and the setting key Press and hold the ON OFF key for about 3 seconds to exit the setup menu Change Batteries NOTICE The two 1 5 V AA batteries must be replaced when the battery capacity indicator flashes 1 Open the lid of the battery compartment 2 Remove used batteries 3 Replace bat...

Страница 9: ...olution 0 01 hPa Overload 300 hPa Accuracy 1 of the MBE Ambient Temperature 0 C 40 C Storage Temperature 20 C 70 C Batteries 2x 1 5 V AA Power Supply 20 mA Size 106 mm x 64 mm x 28 mm Weight 150 g NOTICE Subject to technical changes Status 11 2019 ...

Страница 10: ...ed of in an environmentally friendly manner by an authorised centre NOTICE On request we take back old appliances and dispose of them in an environmentally friendly way To ensure the accuracy of your measuring device we recommend an annu al inspection by an authorised ecom partner In case of heavy use shorter inspection intervals should be chosen please contact your ecom partner ...

Страница 11: ...11 Consumables Spare Parts You can find consumables or spare parts in our webshop at www shop ecom de NOTICE ...

Страница 12: ...ecom GmbH Am Großen Teich 2 D 58640 Iserlohn info ecom de www ecom de Phone 49 2371 945 5 Fax 49 2371 40305 ...