background image

 

 

TP-M11 

14

 
Locate outlets at least 6 inches from 
outside walls or window coverings. 
 
Return Ductwork 
 
Return air plenum should be the same 
cross sectional area as the air handler 
return air opening. In vertical 
installations, a conventional return air 
drop and elbow is acceptable.  IT is 
recommended that the return duct /drop  
be acoustically lined for 6 feet nearest 
the air handler. 
 

Risk of Freezing 

 
Steps must be taken to prevent the hot 
water coil from freezing.  Coils that have 
failed due to freezing and damage 
caused by frozen coils are not covered 
under warranty. 
 
HRV and Fresh air connections 
 

Fresh air and HRV connections to 
ductwork can pose a risk of dumping cold 
air into ductwork during periods of stand-
by or continuous run.  Calculate mixed 
air stream temperatures and provide 
interlock controls to prevent freezing 
conditions. 
 
Evaporator coils 
 
Evaporator cooling coils that are 
mounted above the hot water coil pose a 
risk to the hot water coil in the event that 
the compressor contactor on the 
condenser sticks in the on position.  
When the call for cooling is satisfied, the 
blower will stop running and allow cold 
air from the evaporator coil to fall on to 
the hot water coil.   
 
Attic and crawl spaces 
 
Air handlers may be located in areas 
subject to freezing conditions.  It is 
necessary to protect the hot water coil 
from freezing.   
 

ELECTRICAL 

 

Warning!

 - Make sure unit is properly 

grounded. Locate air handler on a 
separate electric circuit, or use the same 
circuit as the water heater or boiler.  
 
Air handler wiring diagrams are located 
on the blower for easy reference during 
installation and servicing. 
Nameplate data is located on the side of 
the unit.  
 
All air handlers operate on 
115VAC/1ph/60hz line voltage. All 
control circuits are 24 VAC. One leg of 
the 24 VAC is grounded to the chassis. 

Thermostat 

 
The

 thermal-pac™ 

and

 thermal-duct™

 

air handlers are compatible with most 
standard heat/cool, heat pump, “electric 
heat”, “gas heat”, set-back or electronic 
thermostat.   Some electronic 
thermostats (primarily “power robbing” 
types) require the addition of a resistor 
between the W & C terminals 
and the Y & C terminals.  This is usually 
covered in the thermostat instruction 
manual.  A 1,000 ohm, 5 watt resistor on 
each of the W and Y terminals will 
usually be enough to drain the current 
required to power the thermostat.  Some 

Содержание TP30

Страница 1: ...lation Instructions Thermal pac Thermal duct hot water air handler ECOLOGIX HEATING TECHNOLOGIES INC 221 Holiday Inn Dr Cambridge Ontario N3C 3T2 Phone 519 658 4330 Fax 519 658 9384 info ecologix ca www ecologix ca ...

Страница 2: ... SIZING 11 HEAT LOSS 11 AIR HANDLER SELECTION 11 DUCT LAYOUT 12 INSTALLATION 13 AIR HANDLER MOUNTING 13 DUCTWORK 13 RISK OF FREEZING 14 ELECTRICAL 14 THERMOSTAT 14 A C CONDENSING UNIT 15 PUMP EXERCISER 15 START UP PROCEDURES 15 SERVICE AND MAINTENANCE 16 TROUBLESHOOTING 16 THERMOSTAT CALL ERROR 16 PUMP DOES NOT RUN 17 PUMP IS NOISY AT START UP 17 WATER HEATER T P IS WEEPING 17 INSUFFICIENT OR NO H...

Страница 3: ...rk Are the isolation valves full port Restrictive valves will limit performance Are Thermostat connections correct including cooling and continuous run connections Have the packing materials been removed from the blower and the pump Is there an installation manual for the home owner Is the unit accessible Are there clearances for service and component replacement Are the supply plenum and return d...

Страница 4: ...TP M11 4 TYPICAL PLUMBING CONNECTIONS If the water heater has side connections use them for the air handler ...

Страница 5: ...LECTRICAL WIRING DIAGRAM air handler electrical wiring schematic air handler electrical wiring layout XELK103 air handler electrical wiring schematic air handler electrical wiring layout XELK124 with Cycle Timer ...

Страница 6: ...M11 6 For TP75 TDHV 48 and TDHV 60 air handler electrical wiring schematic air handler electrical wiring layout XELK113 air handler electrical wiring schematic air handler electrical wiring layout XELK134 ...

Страница 7: ...5 000 Heating Capacity Btu h 130F water 28 000 56 000 61 000 71 000 Heating Capacity Btu h 140F water 30 000 60 000 66 000 77 000 Heating Capacity Btu h 160F water 37 000 77 000 85 000 100 000 Heating Capacity Btu h 180F water 48 000 95 000 104 000 122 000 USGPM Heating 2 3 4 5 4 5 4 5 Maximum Heating Airflow CFM 800 1200 1400 1900 Max External Static Pressure wc 0 3 0 4 0 5 0 3 Cooling Capacity H...

Страница 8: ... 53 62 69 74 78 86 Heating Capacity MBH 180F water 30 40 65 76 85 91 96 105 USGPM Heating 2 3 2 3 4 5 4 5 4 5 4 5 4 5 4 5 Nominal Airflow CFM 2 360 540 720 900 1080 1260 1440 1800 Max Design ESP Heat Only WC 1 0 0 8 0 9 0 7 0 8 0 6 1 0 0 5 Max Design ESP Heat Cool WC 3 0 9 0 7 0 8 0 4 0 5 0 3 Blower Motor Full Load Amps 4 4 5 5 7 7 10 10 Circulator Full Load Amps 0 6 0 6 0 8 0 8 0 8 0 8 0 8 0 8 1 ...

Страница 9: ...ring special consideration call 519 658 4330 for answers to questions related to sizing installation or trouble shooting for any of Ecologix air handlers or water heaters Ecologix provides you with the quietest operating air handler available By using large capacity high output heating coils the air handlers deliver more heating per volume of air which means warmer delivered air temperatures Therm...

Страница 10: ...iping conform to ASTM B68 or ASTM B88 standards High density aluminum fins provide maximum heat transfer for small coil surface Fan and Motor All fans are wide body dynamically balanced for extra quiet operation Multi directional sleeve bearing motors allow mounting in any direction for maximum installation flexibility Circulating Pump The circulating pump is matched for maximum performance Air ha...

Страница 11: ...MENT SELECTION AND SIZING Proper sizing of system components is crucial for proper operation Steps for sizing and selection 1 Obtain room by room heat loss and or heat gain 2 Determine heating water temperature 3 Select air handler from specification sheet 5 Determine duct layout Heat Loss Make sure a proper room by room heat loss and heat gain for the dwelling is calculated using HRAI ASHRAE or o...

Страница 12: ...s or zones rather than running a single larger duct with tees For applications with 3 or more floors or any application where a large seasonal adjustment in airflow is anticipated parallel main supply ducts must be used Volume dampers in each of the main supply ducts must be installed and must be accessible for seasonal adjustments For example a 4 storey town house will probably require vastly dif...

Страница 13: ...ity of the coil to avoid tube puncture Note Do not put screws into the cabinet directly in front of and behind the coil 3 4 screws can be safely installed on either side of the coil The cabinet is designed so that the return air can be located on either side of the cabinet through the bottom of the cabinet or from the back Position the filter rack so that the filter is readily accessible Install t...

Страница 14: ... for cooling is satisfied the blower will stop running and allow cold air from the evaporator coil to fall on to the hot water coil Attic and crawl spaces Air handlers may be located in areas subject to freezing conditions It is necessary to protect the hot water coil from freezing ELECTRICAL Warning Make sure unit is properly grounded Locate air handler on a separate electric circuit or use the s...

Страница 15: ...rate the pump once a day for 30 seconds NOTE It s first on cycle will be as soon as power is applied to the air handler START UP PROCEDURES Do not start the air handler or water heater until ALL air has been purged 1 Fill the boiler loop or water heater with water but do not start it 2 Purge all air from the boiler heating or domestic water system 3 Purge all air from the space heating loop by clo...

Страница 16: ...e cooling coil to ensure it is free of debris If a plugged air conditioning coil is suspected call a service technician for testing and cleaning Fan and motor Check fan for dust once a year If dirty vacuum or wash to remove dust Keeping the fan blades clean will reduce noise and improve the capacity and efficiency of the heating system Pump The circulating pump is water lubricated and should requi...

Страница 17: ...oil Refer to Maintenance section for filter care and coil cleaning Air in heating loop purge system Inlet and outlet connections to air handler backwards reverse connections Water heater supply tube dip tube is restricted or damaged check and or replace Supply water temperature set too low or not calibrated properly check water temperature In the case of water heater If the temperature has been se...

Страница 18: ...xELR024DPDT2 Blower Relay 24VAC 30 Amp A A A S XELR01TIMER Cycle Timer Pump Exerciser O O O O xELT002 Transformer 24VAC 40 VA S S S S xELT003 Transformer 24VAC 25 VA A A A A xELD002 Door interlock switch S S S S XELM002 EC Blower motor 1 4 HP S XELM003 EC Blower motor 1 3 HP A S XELM004 EC Blower motor 1 2 HP A S XELM006 EC Blower motor 3 4 HP S xBLF105T Blower 10x5T DD S xBLF108 Blower 10x8 DD S ...

Страница 19: ...se or alteration Ø operation of device at temperatures or pressures outside of the rated capacities Ø lime or scale deposits Ø corrosive operating environment Ø equipment moved from original installation location v Replacements furnished under this warranty will be F O B Ecologix Heating Technologies Inc product distribution points in the United States and Canada They will be invoiced at regular p...

Отзывы: