ecoSMART Supervisor user, installer and technical service manual
35
EN
8.3.
Table of electrical connections
DIGITAL OUTPUTS
CONNECTIONS
DESCRIPTION
Connection
terminal
Controller terminal
Type
Signal
Block I / DO1
/ J16 / NO1
Activation 250Vac / 8A max
Brine pump activation
Block I / DO2
/ J17 / Out2
Activation 250Vac / 8A max
Production pump activation
Block I / DO3
/ J18 / Out3
Activation 250Vac / 8A max
Auxiliary brine pump activation
Block I / DO4
/ J19 / Out4
Activation 250Vac / 8A max
Auxiliary pump cool tank activation
Block I / DO5
/ J20 / Out5
Activation 250Vac / 8A max
Passive cooling activation
Block I / DO6
/ J22 / NO6
Activation 250Vac / 8A max
Auxiliary heating system
Block I / DO7
/ J23 / NO7
Activation 250Vac / 8A max
Active cooling activation
Block I / DO8
/ J24 / NO8
Activation 250Vac / 8A max
DHW production activation
Block I / DO9
/ J27 / NO9
Activation 250Vac / 8A max
Free
Block I / DO10
/ J27 / NO10
Activation 250Vac / 8A max
Free
Block I / DO11
/ J28 / NO11
Activation 250Vac / 8A max
Free
Block I / DO12
/ J28 / NO12
Activation 250Vac / 8A max
Free
Block I / DO13
/ J28 / NO13
Activation 250Vac / 8A max
Free
COMMUNICATIONS
CONNECTIONS
DESCRIPTION
Connection
terminal
Controller terminal
Type
Signal
Block II / FBus1
/ J9 FBus1
RS485 ModBus RTU
--
Block II / BMS2
/ J11 BMS2
RS485 ModBus RTU
Remote bus access
--
/ BMS card
Communications card connector
Block II / pLAN
/ J14 pLAN
RS485 ModBus RTU
Communication with heat pumps
Block II / FBus2
/ J29 FBus2
RS485 ModBus RTU
--
ANALOGUE INPUTS
CONNECTIONS
DESCRIPTION
Connection terminal
Controller terminal
Type
Signal
Block II / AI1
/ J2 / U1
NTC 10K 25 °C
Brine circuit outlet temperature probe
Block II / AI2
/ J2 / U2
NTC 10K 25 °C
Brine circuit inlet temperature probe
Block II / AI3
/ J2 / U3
NTC 10K 25 °C
Production circuit outlet temperature probe
Block II / AI4
/ J3 / U4
NTC 50K 25 °C
Production circuit inlet temperature probe
Block II / AI5
/ J3 / U5
NTC 10K 25 °C
Outside temperature probe
Block II / AI6
/ J4 / U6
NTC 10K 25 °C
Free
Block II / AI7
/ J4 / U7
NTC 10K 25 °C
Free
Block II / AI8
/ J5 / U8
NTC 10K 25 °C
Free
Block II / AI9
/ J5 / U9
NTC 10K 25 °C
Free
Block II / AI10
/ J5 / U10
NTC 10K 25 °C
Free
Block II / AI11
/ J5 / U11
NTC 10K 25 °C
Free
Block II / AI12
/ J5 / U12
NTC 10K 25 °C
Free