- 22 -
EN
420010404000
Maxflam D 10-20
-
+
-
+
AIR REGULATION SUCTION SIDE
1 2 3
FIRING HEAD SETTING
ADJUSTMENT DATA
NOZZLE
PUMP
OUTPUT
FIRING HEAD SETTING
AIR DAMPER ADJUSTMENT
gph
spry
bar
kg/h
Pos.
Pos.
1.00
60°HO
23
6
1
2,20
1.25
60°HO
23
8
1
2,80
1.50
60°HO
23
9,5
1
3,50
2.00
60°HO
21
12
2
4,50
1.50
60°HO
23
9,5
1
3,50
2.00
60°HO
23
12,50
2
4,50
2.50
60°HO
23
15,80
2
5,50
3.00
60°HO
23
20
3
8
Maxflam D 10
Maxflam D 20
- At the end of the prepurging, the control box shut off the solenoid valve “O” while opening the 1st stage
valve (for example valve “A”), allowing the burner ignition in Low Flame.
- In order to have a correct combustion, adjust the combustion air flow (see figure).
- The fuel pressure during burner’s working shall be set to 23 bars.
-
L
+
ADJUSTEMENT OF PRESSURE IN PREPURGING PHASE