Max Gas 70 - 105- 120 P AB
MOUNTING TO THE BOILER
+
–
TUBE DISASSEMBLY
–
+
2
3
1
Error code table
Red blink code of
«AL» at
Possible cause
signal lamp (LED))
term. 10
2 blinks
on
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
3 blinks
on
«LP» faulty
- Loss of air pressure signal after «t10», - «LP» welded in normal position
4 blinks
on
Extraneous light when burner is started up
5 blinks
on
Time out «LP»
- «LP» welded in working position
6 blinks
on
Free
7 blinks
on
Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
8 blinks
on
Free
9 blinks
on
Free
10 blinks
off
Wiring error or internal error, output contacts, other faults.
14 blinks
on
CPI contact not closed