11
www.ecoflam-burners.com
EN
420010029304
2
1
4
5
6
3
1
0
Y1
Function
- Oil burner pump
1 suction intake connection.
2 return connection.
3 pressure connection.
4 oil pressure gauge connection.
5 negative pressure gauge connection.
6 oil pressure regulator.
10 Solenoid valve electrical connection.
Y1 fuel-oil solenoid valve.
DANFOSS
BFP 11 R3
The oil burner pump used is a self-priming
gear pump, which must be connected as
two-line pump via a bleed filter. There is an
intake filter and an oil pressure regulator
integrated in the pump. Pressure gauges
for pressure measurements and negative
pressure measurements must be
connected before the equipment is
commissioned.
NB: before starting the burner, check that
the return pipe is open. An eventual
obstraction could damage the pump
sealing device.
One-pipe system
ONE PIPE SYSTEM: If the oil supply
circuit is one-pipe system, the pump
needs to be modified following intructions
in the picture.
3
2
1
With horse-shoe
-shaped washer.
4
1 -
2
3
2
1
1
Without horse-shoe
-shaped washer.
1 -
2
1 Hoses
2 Filter
3 Oil cock
4 Plug
Содержание MAX 12
Страница 60: ...60 www ecoflam burners com 420010029304 RU 3 4 5 5 5 60 6 A 50 100 mm A1 50 100 mm 1 3 4 2 3 5 A A1...
Страница 61: ...61 www ecoflam burners com 420010029304 RU A 230 V 50 60 Hz 5 A 1 fig 1 3 mm 5 6 mm 4 mm 1...
Страница 65: ...65 www ecoflam burners com 420010029304 RU A B A B 1 NB Max 4 8 12 1 2 3 2 3 5 30 C 5 1 No1 No2 No3 2 3...
Страница 66: ...66 www ecoflam burners com 420010029304 RU 1 2 3 4 NB E BCU display...