pag.25
LB 509
BLU 1700.1 - 2000.1 PR / MD
B
Parameter
Display
Ecoflam setting
Ecoflam setting Ecoflam setting
(passive probe)
(passive probe)
(active probe)
QAE22
FT-TP/1000
QBE620-P...
Limit value of limit comparator
AL
0
0
0
Switching differential for limit comparator
HYSt
0
0
0
Proportional band
Pb.1
8
8
1
Derivative time
dt
20
20
3
Integral action time
rt
80
80
15
Dead band (neutral zone)
db
0.5
0.5
0.5
Actuator running time (sec.)
tt
12
12
12
Switch-on threshold burner / stage II
HYS1
-2
-2
-0.2
Switch-off level stage II
HYS2
0
0
0
Upper switch-off threshold
HYS3
5
5
0.5
Response threshold
q
0
0
0
Heating curve slope
H
2
2
2
Parallel displacement
P
0
0
0
PARAMETERS
Parameter
Display
Ecoflam setting
(passive probe)
(active probe) QBE620-P...
QAE22
FT-TP/1000
-P4
-P10
-P16 -P25 -P40
Analog input 1, 2 and 3; setpoint
changeover / shift
C111
9030
5030
G000 G000 G000 G000 G000
Limit comparator; controller type;
setpoint 1; locking
C112
0010
0010
0010 0010 0010 0010 0010
Unit address; decimal place / unit,
signal for out-of-range
C113
0110
0110
0110 0110 0110 0110 0110
Measured value range start analog
input 1
SCL
0
0
0
0
0
0
0
Measured value range
analog input 1
SCH
100
100
4
10
16
25
40
Measured value range
analog input 2
SCL2
0
0
0
0
0
0
0
Measured value range
analog input 2
SCH2
0
0
0
0
0
0
0
Lower setpoint limit
SPL
60
60
0
0
0
0
0
Upper setpoint limit
SPH
88
88
4
10
16
25
40
Actual value correction,analog input 1
OFF1
0
0
0
0
0
0
0
Actual value correction,analog input 2
OFF2
0
0
0
0
0
0
0
Actual value correction,analog input 3
OFF3
0
0
0
0
0
0
0
Filter time constant for digital filter,
dF1
1
1
0
0
0
0
0
analog input 1
CONFIGURATION