14
www.ecoflam-burners.com
EN
420011136900
Start up
- Setting data table - Air regulation
The settings above are
basic settings
. In case of operation at 60 Hz, the burner must be recalibrated by closing the air shutter so as to
reduce the amount of incoming air.
The burner leaves the factory with the following calibration values:
!
Risk of air blast!
Continuously check CO, CO2 and soot emissions when adjusting the output of
the burner. Optimise combustion values in the event of CO formation. CO must
not exceed 50 ppm.
A
B
+
-
1
Low Flame air adjustment (1)
Intervene on screw A in the picture:
• turning it anti-clockwise increases the
flow rate;
• turning it clockwise decreases the
flow rate.
High Flame air adjustment (1)
Intervene on screw B in the picture:
• turning it anti-clockwise increases the
flow rate;
• turning it anti-clockwise decreases the
flow rate.
Firing head setting (2).
Intervene on the screw shown in the
picture:
• turn it using a hex spanner until it
reaches the desired value (index from 0 to
5).
+
-
0
1
2
3
4
2
BURNER
CODE
NOZZLE
PUMP
PRESSURE
BURNER
OUTPUT
FIRING HEAD
SETTING
AIR DAMPER
SETTING
gph
Type
spry
bar
kg/h
Pos.A
I°
II°
3147867
CONFORT 100
1,5
DELAVAN 60°W
11 - 13
6,32
39,5
1,9
3
3147824
SP 110
1,75 DELAVAN 60°W
11 - 14
7,53
39,5
2,2
3,5
3147861
SP 235
3,5
DELAVAN 60°W
10 - 15,5
15,5
29,5
2
3
A