26
MAIN REMOTE CONTROLLER - FLOW SENSOR FLOW RATE RANGE
Adjust the flow sensor minimum flow rate setting from the default value of 5L/min to the required value of 7L/min for the following
models only: EHPT21X-UKHDW1L, EHPT25X-UKHDW1L & EHPT30X-UKHDW1L
The flow sensor flow rate settings can be accessed via the auxiliary settings within the service menu.
MAIN REMOTE CONTROLLER - HEAT PUMP FLOW RATE RANGE
Set the heat pump flow rate settings according to the specific model of heat pump installed.
The heat pump flow rate settings can be accessed via the heat pump settings within the service menu.
Long press
<Main Controller Menu Tree>
Main screen
Initial
Main
menu
Service
Password
protected
Manual operation
Function settings
Thermistor adjustment
Economy settings for pump
Electric heater (Heating)
Electric heater (DHW)
Mixing valve control
Flow sensor
Auxiliary settings
ON/OFF
Delay
ON/OFF
Delay
Running
Interval
Minimum
Maximum
Delay
ON/OFF (Booster heater/Immersion heater)
Menu
Analog output
Priority
Interval
<Main Controller Menu Tree>
Main screen
Initial
Main
menu
Service
Password
protected
Manual operation
Function settings
Thermistor adjustment
Economy settings for pump
Electric heater (Heating)
Electric heater (DHW)
Mixing valve control
Flow sensor
Standard (Heat pump & electric heater)/Heater (Electric heater only)/
Boiler/Hybrid (Heat pump & heater/Boiler)
Auxiliary settings
Heat source setting
Pump speed
ON/OFF
Delay
ON/OFF
Delay
Running
Interval
Minimum
Maximum
Delay
ON/OFF (Booster heater/Immersion heater)
Menu
Analog output
Priority
Interval
Minimum
Maximum
Heat pump settings
Quiet mode
Long press
Heat Pump Flow Rate Table
Model
Minimum (L/min)
Maximum (L/min)
PUZ-WM50VHA
7
14
PUZ-WM60VAA
9
17
PUZ-WM85V(Y)AA
11
24
PUZ-WM112V(Y)AA
15
32
PUZ-HWM140V(Y)HA
18
40
MAIN REMOTE CONTROLLER - FLOW RATE LOOK UP
The heat pump primary flow rate can be viewed by inputting request code 540 into the running information setting within the
service menu.
WIRING
All electrical wiring should be carried out by a competent electrician and be in accordance with the latest I.E.E. Wiring
Regulations.
The Pre-plumbed cylinder thermal controls and circulating pumps are factory pre-wired. Further wiring will be required between
the FTC6 controller, the programmer, room temperature sensor and the Heat Pump. Additional controls and wiring will be
required if a second space heating zone is to be fitted to the installation.
Any thermal controls and over-temperature thermal cut-outs MUST NOT be bypassed.
The mains supply must be via a double pole isolating switch with a contact separation of at least 3mm in both poles. The
supply must be fused 16 amp. A supply cable of minimum 2.5mm
2
cross sectional area should be used.
THIS APPLIANCE MUST BE EARTHED