8

Installation Instruction

Settlement of outdoor unit

Anchor the outdoor unit with a bolt and 
nut  

10 or  8 tightly and horizontally 

on a concrete or rigid mount.

Fit  the seal  into the drain  elbow, then  insert  
the  drain  joint  into the base pan hole of 
outdoor unit, rotate  90

to securely  assemble

them. Connecting the drain joint with   an   
extension   drain   hose (Locally purchased), 
in case of the water draining off the outdoor unit
during the heating mode.

Drain joint installation 

Seal

Drain joint

Base pan hole of
outdoor unit

Seal

Drain pipe

Fig.13

REFRIGERANT PIPING CONNECTION

Oblique

90

Roughness

Burr

Main cause for refrigerant leakage
is due to defect in the flaring work. 
Carry out correct flaring work
using the following procedure:

A: Cut the pipes and the cable.

1. Use the piping kit accessory or pipes 
    purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than the measured distance.
4. Cut the cable 1.5m longer than the pipe length.

1. Flaring work

Fig.14

A

B

Air inlet 

Air outlet

Air inlet 

Fig.12

B: Burr removal

1. Completely remove all burrs from the cut 
     cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a 
    downward direction as you remove burrs in 
    order to avoid dropping burrs into the tubing.

Pipe

Reamer

Point down

Fig.15

Outdoor unit dimension
          mm(WxHxD)

A(mm)

458

460

B(mm)

250

276

530

290

560

335

549

276

Mounting dimensions

700x535x235

685x430x260

780x540x250

760x590x285

845x695x335

590

333

895x860x330

Содержание ECO1202S

Страница 1: ...eference Before using your air conditioner please read this manual carefully and keep it for future reference Before using your air conditioner please read this manual carefully and keep it for future...

Страница 2: ...ust be connected to the terminal which is marked with the letter N or coloured BLACK The BROWN wire is the LIVE and must be connected to the terminal which is marked with the letter L or coloured RED...

Страница 3: ...nit by yourself Improper installation will cause water leakage electrical shock or fire Please consult authorized dealer or specialist for the installation work Please note fault caused by improper in...

Страница 4: ...f the outdoor unit are not attached securely it could result in a fire or electrical shock due to dust water etc Perform electrical work according to the installation manual and be sure to use an excl...

Страница 5: ...Outdoor unit If an awning is built over the outdoor unit to prevent direct sunlight or rain exposure make sure that heat radiation from the condenser is not restricted Ensure that the clearance aroun...

Страница 6: ...minimise vibration excessive noise The indoor unit should be installed on the wall at a height of 2 3 metres or more from the floor Two of the A B and C directions should be free from obstructions CA...

Страница 7: ...allation plate Dimensions are in mm unless otherwise stated Wall Indoor Outdoor 5 7mm Fig 6 INSTALLATION INSTRUCTIONS A 40 B Right rear side refrigerant pipe hole 65 Installation plate Indoor unit out...

Страница 8: ...rom side to side to see that it is securely hooked 3 Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping...

Страница 9: ...hose sloped downward to drain out the con densed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction wher...

Страница 10: ...o defect in the flaring work Carry out correct flaring work using the following procedure A Cut the pipes and the cable 1 Use the piping kit accessory or pipes purchased locally 2 Measure the distance...

Страница 11: ...RK Electric safety regulations for the initial Installation 1 If there is serious safety problem about the power supply the technicians should refuse to install the air conditioner and explain to the...

Страница 12: ...10 Electrical work Fig 20 Fig 21 Electrical control box cover Panel 10mm 10mm 40mm 40mm Cooling only type Cooling heating type Code wire Or 10mm 40mm Cooling heating type Terminal block of indoor uni...

Страница 13: ...cure the cable onto the control board with the cord clamp 1 Remove the electrical control board cover from the outdoor unit by loosening the screw 2 Connect the connective cables to the terminals as i...

Страница 14: ...hall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION CAUTION CAUTION AIR PURGING Air and moisture in the refr...

Страница 15: ...of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation slightly loose the flare nut of the Lo valve on the gas pipe side and check that the air is entering Operation no...

Страница 16: ...ck 1 Soap water method Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of th pi...

Страница 17: ...MEMO Date of installation Purchased from Dealer Name Date of purchase Model number Serial number...

Страница 18: ...ing from a faulty installation is specifically excluded This unit must be operated under conditions as recommended at voltages indicated on the unit Any attempts made to service or modify the unit by...