Troubleshooting 

 

Trouble codes are output as LED flashes and as signal output pulses. The pulses are active 

low, so the signal will be pulled low for each pulse. In voltage output mode, 0V indicates a 

low  state.  In  current  output  mode,  4mA  indicates  a  low  state.  This  allows  for  both  visual 

indication as well as indication for the integrated diagnostic system. 

 

Failure Mode 

Judgment Condition 

Action After Failure Condition 

 

 

Heater 

Stop 

Code 

Heater Open 

Off 

x1 

Heater Shorted 

Off 

x2 

Under or over Vbat 

Vbat<11V or Vbat>28V 

Off 

x3 

Vs too high 

VVS>3.7V(Vs>1.7V) 

On 

x4 

 
Codes: The codes represent the number of times the output is pulled low. 

For example: 
x1 – One 125ms pulse every 2 seconds 
x2 – Two 125ms pulses every 2 seconds 
x3 – Three 125ms pulses every 2 seconds 
x4 – Four 125ms pulses every 2 seconds 
See figure below for the code waveform diagram. 
 

 

 

Содержание XCM114

Страница 1: ...XCM114 O2 Lambda AFR Module Instruction Manual 07 15 2014 P N XCM114 4...

Страница 2: ...this manual may be photocopied or reproduced in any form without prior written consent from ECM ENGINE CONTROL AND MONITORING Information and specifications subject to change without notice XCM114 is...

Страница 3: ...nment where an oxidizer and fuel exist because the sensor may ignite the mixture Important Operation Notes 1 Before installing the O2 sensor apply a small amount of non lead containing antiseize compo...

Страница 4: ...4 XCM114 Kit Contents Not pictured This instruction manual P N XCM114 4...

Страница 5: ...rom 12 to 48 from the exhaust valve s of the engine Mount the O2 sensor in a location where liquids ex condensed water will not collect on the sensor Lightly coating its threads with a non lead contai...

Страница 6: ...aged sensors 1 Hold the sensor in quiescent air for at least 20 minutes Measure Vout or Iout and determine the O2 in the air from Appendix A Denote this O2 as O2cal and the measured Vout or Iout as Vc...

Страница 7: ...le should be interpreted as 0 i e there are no O2 molecules in the mixture Negative values are given for use in calculating Lambda AFR using the table below where it indicates a rich mixture O2 vs Lam...

Страница 8: ...rrected Lambdameasured B x P 1 B x P Equation 3b where Lambdacorrected the Lambda corrected for exhaust pressure Lambdameasured the Lambda output by the AFM B 0 000627 for Lambda 1 0 rich B 0 000830 f...

Страница 9: ...nected internally Current output mode using internal Int power i e Current Transmitter Type 3 Current output mode using external Ext power i e Current Transmitter Type 4 1 RDAQ in 4 20mA systems is ty...

Страница 10: ...on each side of the module and slide the PCB out of the enclosure 3 The switches for mode and current output power source are located on the lower left of the board labeled S3 S4 Set the position of t...

Страница 11: ...ed to the left Do not change the blue potentiometer adjacent to it Type Switches On Vout Range Iout Range 1 2 6 0 5 to 2 5 V 5 to 9 mA 2 2 7 2 5 to 4 5 V 9 to 12 mA 3 2 8 3 5 to 5 5 V 11 to 15 mA 4 4...

Страница 12: ...r the integrated diagnostic system Failure Mode Judgment Condition Action After Failure Condition Heater Stop Code Heater Open Off 1 x1 Heater Shorted Off 1 x2 Under or over Vbat Vbat 11V or Vbat 28V...

Страница 13: ...press implied or arising by operation of law trade usage or course of dealing are hereby disclaimed The warranty is void if the control module is opened or the wiring harness is modified LIMITATION OF...

Страница 14: ...926 5 294 5 685 6 101 6 543 7 013 7 513 8 045 8 609 10 9 209 9 844 10 518 11 231 11 987 12 788 13 634 14 530 15 477 16 477 20 17 535 18 650 19 827 21 068 22 377 23 756 25 209 26 739 28 349 30 043 30 3...

Страница 15: ......

Страница 16: ...Los Altos CA 94023 0040 USA 408 734 3433 Fax 408 734 3432 www ecm co com...

Отзывы: