Eclipse Veri-Flame 5602 Скачать руководство пользователя страница 2

2

Eclipse Model 5602 Tester, Instruction Manual 819  2/11/2011

Veri-Flame No-Purge Models 5602-3x and 5605-3x

Do NOT use the modulation relay board for these controllers.

Test Procedure - set initial switch settings

1) Turn on the POWER switch, the POWER light will come on. 

2) Turn on the LIMITS switch. The green “INTERLOCKS CLOSED” light on the

controller will come on. Then the SPARK and PILOT lights on the tester will

come on. 

3) Set the FLAME switch to the appropriate position for the flame sensor type of

the model under test: FR (down) for flame rods, UV/IR (up) for ultraviolet

scanners. 

4) Observe that the red light inside the FLAME SIGNAL test jack comes on. At

the end of TFI (trial for ignition) time, the SPARK light will go off. Then about 5

seconds after the TFI ends, the MAIN light will come on. If interrupted pilot is

selected (DIP-Switch 2 is off), the PILOT light will go off after about 10

seconds. 

5) Set the FLAME switch to EXT. 

a)  For non-recycling selection (DIP-Switch 1 is off), the red “FLAME

FAILURE” light on the controller will come on within 4 seconds. The

ALARM light on the tester will also come on. 

b)  For recycling selection (DIP-Switch 1 is on) and the flame indicator has

been on for more than 35 seconds, the unit will turn off the MAIN (and

PILOT if on) and recycle to the beginning self-check sequence. Then the

SPARK and PILOT will come on as in step 2 above. Leave the FLAME

switch at EXT. The red “FLAME FAILURE” light on the controller will come

on after the trial for ignition. The ALARM light on the tester will also come

on.

6) With the control in the ALARM condition, set the DAMPER switch to FAIL

(center position). Reset the controller by pressing the pushbutton once to the

in position and pressing it again to bring it back out. 

7) Observe that the “SYSTEM ERROR” light flashes for a couple seconds and

then comes on steady. Also the tester ALARM light comes on. Return the

DAMPER switch to VER-OK. 

8) Place the LIMITS switch to OFF and reset the controller. Turn the FLAME

switch to the appropriate position for the flame sensor type. Observe the red

light inside the FLAME SIGNAL test jack. The “SYSTEM ERROR” light will

start flashing. Wait about 25 seconds and the ALARM light will come on.

Veri-Flame Purge Models 5602-2x and 5605-2x

Do NOT use the modulation relay board for these controllers.

Test Procedure - set initial switch settings

1) Turn on the POWER switch, the POWER light will come on. 

2) Turn on the LIMITS switch. The green “INTERLOCKS CLOSED” light on the

controller will come on. In less than 5 seconds, the FAN light on the tester will

come on. 

3) The unit will stay in this sequence for the selected purge time, then the SPARK

and PILOT lights on the tester will come on.

4) Set the FLAME switch to the appropriate position for the flame sensor type of

the model under test: FR (down) for flame rods, UV/IR (up) for ultraviolet

scanners.

No Purge Model

Purge Model

Содержание Veri-Flame 5602

Страница 1: ...ies Tester Check the controller model number and DIP Switch settings to be sure that the recycling pilot mode trial for ignition purge time and post purge settings are correct for your application Be sure the modulation relay board is installed for modulation model controllers 560x 4x and unplugged for non modulating controllers Before plugging in the power cord of the tester seat the controller f...

Страница 2: ... will come on as in step 2 above Leave the FLAME switch at EXT The red FLAME FAILURE light on the controller will come on after the trial for ignition The ALARM light on the tester will also come on 6 With the control in the ALARM condition set the DAMPER switch to FAIL center position Reset the controller by pressing the pushbutton once to the in position and pressing it again to bring it back ou...

Страница 3: ...conds later the AIR FAILURE light on the controller and the ALARM light on the tester will both come on 10 Set the AIR switch to SHORT down position Reset the controller and observe that the SYSTEM ERROR light flashes for about 15 seconds Then the SYSTEM ERROR light comes on steadily and the ALARM light on the tester comes on Return the AIR switch to the NORMAL position 11 Place the LIMITS switch ...

Страница 4: ...n the DAMPER switch to VER OK 10 Set the LOW FIRE switch to OPEN Reset the controller The controller will sequence as in steps 2 and 3 above At the end of the low purge time the SYSTEM ERROR light and the ALARM light come on Return the LOW FIRE switch to the CLOSED position 11 Set the AIR switch to FAIL center position Reset the controller The FAN light will come on and about 10 seconds later the ...

Отзывы: