Eclipse Veri-Flame Tester

and Trainer

Model 5602

Instruction Manual 819

2/11/2011

The Model 5602 Tester (pn 49602) provides a convenient means for testing
Veri-Flame controllers and sensors. It also is a good tool for learning about
the sequences and safety features of all the Veri-Flame models. Features
include:

•  7 Toggle switches for simulating inputs 

•  9 Lights for controller output status

•  2 Quick-connect terminals for external flame sensor 

•  Built in flame simulators 

•  Tests 120V or 240V supply models

 NOTE:

        

The tester is supplied with a standard North American 120VAC plug. The 

plug can be cut off and the remaining powercord can be attached to an 

appropriate plug or terminal for  240VAC supply.

     CAUTION:

 

The tester must be supplied with the voltage level that matches the Veri-

Flame model being tested. 

     CAUTION:

  Before beginning the test procedures, read the Eclipse Combustion

Instruction Manual 818 and become thoroughly familiar with the controller

model that you are testing. 

                         Mounting Controllers to the 5602 Series Tester

Check the controller model number and DIP-Switch settings to be sure that the

recycling, pilot mode, trial-for-ignition, purge time, and post purge settings are

correct for your application. Be sure the modulation relay board is installed for

modulation model controllers (560x-4x) and unplugged for non-modulating

controllers. Before plugging in the power cord of the tester, seat the controller

firmly in place over the opening on the face of the 5602 Series Tester.

    WARNING:

Risk of electrical shock. High voltage is exposed when tester is plugged in

but the Veri-Flame control is removed. 

           NOTE:

Intermittent pilot operation (DIP-Switch 2 on) means the pilot stays on during

the burner run period. Interrupted pilot (DIP-Switch 2 off) means the pilot will

turn off after the main flame has established.

 

                                

CAUTION:

Remove any external flame sensors from the connector block S1 and S2

when using the internal flame simulator. 

           NOTE:

The internal flame simulators are factory preset. Some adjustment of the UV

signal is possible by turning U.V. SENS. adjustment (on the rear).

Relay Board

Initial Switch Settings:

                               POWER:    OFF
                               LIMITS:      OFF
                               AIR:              NORMAL

DAMPER:       VER-OK
FLAME:          EXT
LOW FIRE:     CLOSED
VALVE:          CLOSED  

Model 5603-40-4
Part No. 49240-2

Содержание Veri-Flame 5602

Страница 1: ...ies Tester Check the controller model number and DIP Switch settings to be sure that the recycling pilot mode trial for ignition purge time and post purge settings are correct for your application Be sure the modulation relay board is installed for modulation model controllers 560x 4x and unplugged for non modulating controllers Before plugging in the power cord of the tester seat the controller f...

Страница 2: ... will come on as in step 2 above Leave the FLAME switch at EXT The red FLAME FAILURE light on the controller will come on after the trial for ignition The ALARM light on the tester will also come on 6 With the control in the ALARM condition set the DAMPER switch to FAIL center position Reset the controller by pressing the pushbutton once to the in position and pressing it again to bring it back ou...

Страница 3: ...conds later the AIR FAILURE light on the controller and the ALARM light on the tester will both come on 10 Set the AIR switch to SHORT down position Reset the controller and observe that the SYSTEM ERROR light flashes for about 15 seconds Then the SYSTEM ERROR light comes on steadily and the ALARM light on the tester comes on Return the AIR switch to the NORMAL position 11 Place the LIMITS switch ...

Страница 4: ...n the DAMPER switch to VER OK 10 Set the LOW FIRE switch to OPEN Reset the controller The controller will sequence as in steps 2 and 3 above At the end of the low purge time the SYSTEM ERROR light and the ALARM light come on Return the LOW FIRE switch to the CLOSED position 11 Set the AIR switch to FAIL center position Reset the controller The FAN light will come on and about 10 seconds later the ...

Отзывы: