Configuration
8/05
UDC2500 Universal Digital Limit ControllerProduct
Manual
41
Function Prompt
Lower Display
Selection or Range of Setting
Upper Display
Parameter
Definition
Thermocouple Input is in imminent danger of
failing. Not valid for input types other than
Thermocouple.
A1S1VA
Value in engineering units
ALARM 1 SETPOINT 1 VALUE
—This is the
value at which you want the alarm type
chosen in prompt A1S1TYPE to actuate. The
value depends on what the setpoint has
been configured to represent. No setpoint is
required for alarms configured for
Communications SHED.
This prompt does not appear for Alarm
Types that do not use values. For example:
A1S1TY = MANUAL.
A1S1HL
HIGH
LOW
ALARM 1 SETPOINT 1 STATE
—Select
whether you want the alarm type chosen in
prompt A1S1TYPE to alarm High or Low.
HIGH ALARM
LOW ALARM
A1S2TY
ALARM 1 SETPOINT 2 TYPE
—Select what
you want Setpoint 2 of Alarm 1 to represent.
The selections are the same as A1S1TYPE.
A1S2VA
Value in engineering units
ALARM 1 SETPOINT 2 VALUE
—This is the
value at which you want the alarm type
chosen in prompt A1S2TYPE to actuate.
The details are the same as A1S1 VAL.
A1S2HL
HIGH
LOW
ALARM 1 SETPOINT 2 STATE
—Same as
A1S1HL.
A2S1TY
ALARM 2 SETPOINT 1 TYPE
—Select what
you want Setpoint 1 of Alarm 2 to represent.
The selections are the same as A1S1TYPE.
ATTENTION
Not applicable with Relay
Duplex unless using Dual Relay PWA.
A2S1VA
Value in engineering units
ALARM 2 SETPOINT 1 VALUE
—This is the
value at which you want the alarm type
chosen in prompt A2S1TYPE to actuate.
The details are the same as A1S1 VAL.
A2S1HL
HIGH
LOW
ALARM 2 SETPOINT 1 STATE
—Same as
A1S1HL.
Содержание UDC2500 Limit
Страница 1: ...Eclipse Universal Digital Controller UDC2500 Limit Control Model 08 2005 Information Guide 925 1...
Страница 2: ...ii UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 10: ......
Страница 76: ...Input Calibration 66 UDC2500 Universal Digital Limit ControllerProduct Manual 8 05...
Страница 126: ......
Страница 127: ......
Страница 128: ......