Eclipse

®

Model 706 

F

oundation

fieldbus™ 

operating Manual

Software Version 1.x

High Performance, 4th Generation

Guided Wave Radar

Level Transmitter

2014/68/EU

Содержание 706GWR

Страница 1: ...Eclipse Model 706 Foundation fieldbus operating Manual Software Version 1 x High Performance 4th Generation Guided Wave Radar Level Transmitter 2014 68 EU ...

Страница 2: ...rotection provided by equipment may be impaired Notice of Copyright and Limitations Copyright 2017 Magnetrol International All rights reserved MAGNETROL MAGNETROL logotype and ECLIPSE are registered trademarks of Magnetrol International Performance specifications are effective with date of issue and are subject to change without notice MAGNETROL reserves the right to make changes to the product de...

Страница 3: ... 4 Signal Characterizer Block SC 30 4 0 Model 706 Transmitter Configuration 32 4 1 Configuration Information 32 4 2 Menu Transversal and Data Entry 33 4 2 1 Navigating the Menu 33 4 2 2 Data Selection 33 4 2 3 Entering Numeric Data Using Digit Entry 34 4 2 4 Entering Numerica Data Using Increment Decrement 34 4 2 5 Enter Character Data 35 4 3 Password Protection 36 4 4 Model 706 Menu Step By Step ...

Страница 4: ...s in which the two wires carry a single variable the varying 4 20 mA current a dig ital communications scheme such as FOUNDATION field bus considers the two wires as a network The network can carry many process variables as well as other information The ECLIPSE Model 706FF transmitter is a FOUNDA TION fieldbus registered device that communicates with the H1 FOUNDATION fieldbus protocol operating a...

Страница 5: ...les that may be needed 1 2 1 Foundation fieldbus dd Revision table 1 3 Link Active Scheduler LAS The default operating class of the Eclipse Model 706FF with FOUNDATION fieldbus is a Basic device However it is capable of being configured as a Link Active Scheduler LAS The LAS controls all communication on a FOUNDATION fieldbus segment It maintains the Live List of all devices on a segment and coord...

Страница 6: ...e distributed along its entire length Therefore the stored energy during a fault will be less and more devices are permitted on a pair of wires Instead of the conservative entity model which only allows about 90 mA of current the FISCO model allows a maxi mum of 110 mA for Class II C installations and 240 mA for Class II B installations FISCO certifying agencies have limited the maximum seg ment l...

Страница 7: ...an algorithm inputs and outputs and a user defined name The Transducer Block TB output is available to the net work through the Analog Input AI blocks Refer to Section 2 3 for additional information on the Transducer Blocks The AI blocks take the TB values and make them available as an analog value to other function blocks The AI blocks have scaling conversion filtering and alarm functions Refer t...

Страница 8: ... mode the target mode the permitted mode s and the normal mode of operation of a block Target The mode to go to Actual The mode the block is currently in Permitted Allowed modes that target may take on Normal Most common mode for target NOTES 1 It may be required to change the the MODE_BLK target parame ter to OOS out of service to change configuration parameters in that specific function block Wh...

Страница 9: ...number which is 0x000156 DEV_TYPE The model number of the ECLIPSE Model 706 FF transmitter 0x0005 It is used by the Host System and other fieldbus interface devices to locate the Device Descriptor DD file DEV_REV Contains the firmware revision of the ECLIPSE Model 706 FF transmitter and is used by the Host System and other fieldbus interface devices to correctly select the associated DD DD_REV Con...

Страница 10: ...ssing time that is free to process additional blocks SHED_RCAS The time duration at which to give up com puter writes to function block RCas locations SHED_ROUT The time duration at which to give up computer writes to function block ROut locations FAULT_STATE SET_FSTATE CLR_FSTATE These only apply to output function blocks The Model 706FF has no output function blocks MAX_NOTIFY The maximum number...

Страница 11: ...he COMPATIBILITY_REV is defined by the device developer and manufacturer In such device replacement scenario the DEV_REV value of the replaced device is equal or greater than the COMPATIBILITY_REV value of the new device 2 2 2 additional Resource Block Parameters Additional parameters are available within the resource block for use with NE 107 to aid in communicating device conditions to the user ...

Страница 12: ...ry FD_FAIL_ALM Used to broadcast a change in the associ ated active conditions which are not masked for the FAIL alarm category FD_OFFSPEC_ALM Used to broadcast a change in the associated active conditions which are not masked for the OFFSPEC alarm category FD_MAINT_ALM Used to broadcast a change in the associated active conditions which are not masked for the MAINT alarm category FD_CHECK_ALM Use...

Страница 13: ...RDWARE_VERSION Read only parameter that corre sponds to Hardware Version in the Transducer Block 2 3 Transducer Block The three TRANSDUCER blocks TB contained within the ECLIPSE Model 706 FF transmitter are custom blocks containing parameters that are pertinent to the transmitter itself TRANSDUCER Block 1 used for level and interface oper ation contains information such as the Configuration Diagno...

Страница 14: ...vision level Please refer to the DD Revision Table Section 1 2 1 Please refer to Appendix A for a complete list of the three Transducer Block parameter sets 2 3 2 Password Parameters To change a parameter at the local user interface a value matching the user password must be entered Default 1 If a static parameter is changed from the local user interface the Associated Transducer Block goes Out of...

Страница 15: ... The ANALOG INPUT AI block takes the ECLIPSE Model 706 FF input data selected by channel number and makes it available to other function blocks at its output The channel selections are 2 4 1 ai Block Parameters The following are general descriptions of the parameters common to all function blocks Additional information for a given parameter may be described later in a section that describes the sp...

Страница 16: ... Most common mode for target PV Either the primary analog value for use in executing the function or a process value associated with it OUT The primary analog value calculated as a result of executing the function block SIMULATE Allows the transducer analog input or output to the block to be manually supplied when simulate is enabled When simulate is disabled the simulate value and status track th...

Страница 17: ...CK_ALM The block alarm is used for all configura tion hardware or system problems in the block ALARM_SUM The current alert status unacknowledged states unreported states and disabled states of the alarms associated with the function block ACK_OPTION Selection of whether alarms associated with the function block will be automatically acknowledged ALARM_HYS Amount the PV must return within the alarm...

Страница 18: ...suitable engineering units 3 The SIMULATE parameter is active 4 AI block MODE is O S out of service NOTE This can be caused by the Resource Block being OOS or the AI Block not scheduled for execution 5 L TYPE not set or set to Direct with improper OUT_SCALE The AI block uses the STATUS_OPTS setting and the TRANSDUCER PV LIMIT value to modify the AI PV and OUT QUALITY A Damping Filter is a feature ...

Страница 19: ...ion etc the value displayed will not reflect the transducer measurement 2 4 3 1 AI Out Display Screens The Analog Input Block Out values can be conditionally displayed as part of the rotating home menu screens A representative example is shown at left The screens will be formatted as shown with Physical Device Tag Selectable Measured Value Status Bad Good Uncertain Bar Graph For example AI1_Level ...

Страница 20: ...ffset 15 5 XD Scale EU at 0 0 XD Scale EU at 100 81 3 XD Scale Units cm Out Scale EU at 0 0 Out Scale EU at 100 81 3 Out Scale Units cm L Type Direct Probe Probe Length 111 cm 81 3 cm 0 cm 81 3 cm 0 cm Offset 15 5 cm Transducer Block LCD Level AI Block Output To FF segment Configuration Probe Length PL Level Offset 0 XD Scale EU at 0 0 XD Scale EU at 100 PL XD Scale Units in cm Out Scale EU at 0 0...

Страница 21: ...3 for additional information on the SOFT_SIMULATION_DISABLE parameter in the resource block 2 5 PID Block The PID Function Block contains the logic necessary to perform Proportional Integral Derivative PID control The block provides filtering set point and rate limits feed forward support output limits error alarms and mode shedding Although most other function blocks perform functions specific to...

Страница 22: ..._HI_ALM The DV HI alarm data DV_HI_LIM The setting for the alarm limit used to detect the deviation high alarm condition DV_HI_PRI The priority of the deviation high alarm DV_LO_ALM The DV LO alarm data DV_LO_LIM The setting for the alarm limit used to detect the deviation low alarm condition DV_LO_PRI The priority of the deviation low alarm FF_GAIN The feedforward gain value FF_SCALE The high and...

Страница 23: ...igh and low scale values associated with OUT PV The process variable use in block execution PV_FTIME The time constant of the first order PV filter PV_SCALE The high and low scale values associated with PV RATE The derivative action time constant RCAS_IN Target setpoint and status that is provided by a supervisory host RCAS_OUT Block setpoint and status that is provided to a supervisory host RESET...

Страница 24: ...ables over time The block compares the integrated or accumulated value to pre trip and trip limits and generates discrete output signals when the limits are reached ST_REV The revision level of the static data associated with the function block TAG_DESC The user description of the intended applica tion of the block STRATEGY The strategy field can be used to identify grouping of blocks ALERT_KEY Th...

Страница 25: ... discrete output TIME_UNIT1 Converts the rate time units in seconds TIME_UNIT2 Converts the rate time units in seconds UNIT_CONV Factor to convert the engineering units of IN_2 into the engineering units of IN_1 PULSE_VAL1 Determines the mass volume or energy per pulse PULSE_VAL2 Determines the mass volume or energy per pulse REV_FLOW1 Indicates reverse flow when true 0 Forward 1 Reverse REV_FLOW2...

Страница 26: ...status Good is PCT_INCL GOOD_LIM UNCERTAIN_LIMIT Sets the limit for PCT_INC OUT receives the status uncertain if PECT_INC UNCERT LIM OP_CMD_INT Operator command RESET Resets the totalizer OUTAGE_LIMIT The maximum tolerated duration for power failure RESET_CONFIRM Momentary discrete value with can be written by a host to enable further resets if the option Confirm reset in INTEG_OPTIONS is chosen U...

Страница 27: ...in the host for sorting alarms etc MODE_BLK The actual target permitted ad normal modes of the block Target The mode to go to Actual The mode the block is currently in Permitted Allowed modes that target may take on Normal Most common mode for target BLOCK_ERR This parameter reflects the error status associated with the hardware or software components associ ated with a block It is a bit string so...

Страница 28: ...proportional gain multiplier value for IN_2 BIAS_IN_3 The bias value for IN_3 GAIN_IN_3 The proportional gain multiplier value for IN_3 COMP_HI_LIM Determines the high limit of the com pensation input COMP_LO_LIM Determines the low limit of the com pensation input ARITH_TYPE The set of 9 arithmetic functions applied as compensation to or augmentation of the range extended input BAL_TIME Specifies ...

Страница 29: ...n may be used in the host for sorting alarms etc MODE_BLK The actual target permitted and normal modes of the block Target The mode to go to Actual The mode the block is currently in Permitted Allowed modes that target may take on Normal Most common mode for target BLOCK_ERR This parameter reflects the error status associated with the hardware or software components associ ated with a block It is ...

Страница 30: ...to force a given input to be used UPDATE_EVT This alert is generated by any change to the static data BLOCK_ALM The block alarm is used for all configura tion hardware connection failure or system problems in the block BLOCK_ERR_DESC Reports more specific details regard ing some errors reported through BLOCK_ERR 3 4 Signal Characterizer Block SC The Signal Characterizer SC function block character...

Страница 31: ...f the variable correspond ing to the x axis for display It has no effect on the block Y_RANGE The display scaling of the variable correspond ing to the y axis for display It has no effect on the block GRANT_DENY Options for controlling access of host computers and local control panels to operating tuning and alarm parameters of the block IN1 The block input value and status IN2 The block input val...

Страница 32: ...ailable for Level Only applications 1 Refer to Section 2 6 5 for configuration menus for Interface Volume or Flow applications 2 These configuration steps are not necessary if the transmitter was pre configured prior to shipment display Question answer Level Units What units of measurement will be used inches millimeters centimeters feet or meters _____________ Probe Model What probe model is list...

Страница 33: ...he previous item in the menu branch DOWN moves to the next item in the menu branch BACK moves back one level to the previous higher branch item ENTER enters into the lower level branch or switches to the entry mode Holding the ENTER down on any highlighted menu name or parameter will show help text for that item 4 2 2 Data Selection This method is used for selecting configuration data from a speci...

Страница 34: ...t may increase by a factor of 10 after the value has been incremented 10 times Down Decrements the displayed value If held down the digits scroll until the push button is released Depending on which screen is being revised the decrement amount may increase by a factor of 10 after the value has been decremented 10 times Back Returns to the previous menu without changing the original value which is ...

Страница 35: ...longer password protected and any value in the basic user menus can be adjusted without entering a confirming password NOTE If a User Password is not known or has been misplaced the menu item New Password in the DEVICE SETUP ADVANCED CONFIG menu displays an encrypted value representing the present password Contact Technical Support with this encrypted password to retrieve the original User Passwor...

Страница 36: ...ement type from the following selections Level Only Interface Level Level Volume Flow HOME SCREEN The Home Screen consists of a slide show sequence of Measured Values screens which are rotated at 2 second intervals Each Home Measured Value screen can present up to four information items Physical Device Tag Measured Value Label Numerical Value Units Status Will be displayed as text Bar Graph shown ...

Страница 37: ...ted over a parameter or menu will provide additional information about that item DEVICE SETUP Choosing DEVICE SETUP from the MAIN MENU will result in an LCD presentation as shown at left The small down arrow shown at the right hand side of the screen is the indication that more items are available below and can be accessed by pressing the DOWN key Section 2 6 5 shows the entire tree menu for the M...

Страница 38: ...P 7YF Sngl Rod Std 7YG Sngl Rod Std 7YJ Sngl Rod HTHP Cages 7YL Sngl Rod HP Cages 7YM Sngl Rod HP Tanks 7YN Sngl Rod HTHP Tanks 7YP Coax HP 7YS Coax Steam 7YT Coax Std 7Y1 Sngl Flex Std 7Y2 Sngl Flex Bulk 7Y4 Sngl Flex Cages 7Y5 Twin Flex Bulk 7Y6 Sngl Flx HTHP Cage 7Y7 Twin Flex Clad Probe Coating 7yF only None Bare PFA Coated Probe Mount NPT BSP Flange NPT Flushing BSP Flushing Flange Flushing H...

Страница 39: ... and Level Flow Home Screen Main Menu Device Setup Quick Start Identity Basic Config I O Config Display Config Advanced Config Factory Config Measurement Type Level Only Interface and Level Volume and Level System Units Flow Probe Model 7YD Coax HTHP 7YF Sngl Rod Std 7YG Sngl Rod Std 7YJ Sngl Rod HTHP Cages 7YL Sngl Rod HP Cages 7YM Sngl Rod HP Tanks 7YN Sngl Rod HTHP Tanks 7YP Coax HP 7YS Coax St...

Страница 40: ... Type Linear Spline CUSTOM TABLE VALUES Up to 30 Pairs of Head Flow Data Reference Distance 11 8 inches to 100 feet 30 cm to 30 m Maximum Head calculated read only Maximum Flow calculated read only Low Flow Cutoff 0 to 9999999 cubic ft min TOTALIZER SETUP Units Cubic Feet Gallons Mil Gallons Liters Mil Liters Cubic Meters NON RESET TOTALIZER Units Cubic Feet Gallons Mil Gallons Liters Mil Liters C...

Страница 41: ...de View Upr Thickness Interface and Level mode only Hide View Volume Volume and Level mode only Hide View Flow Flow mode only Hide View Head Flow mode only Hide View Distance Hide View NRTotalizer Flow mode only Hide View R Totalizer Flow mode only Hide View Echo Strength Interface and level mode only Hide View Ifc Echo Strength Interface and level mode only Hide View Elec Temp Hide View Probe Bui...

Страница 42: ...trength units Sloped End Dist used when Lvl Thresh Mode is Sloped 25 to 100 feet 7 to 30 m Ifc Lvl Thresh Mode Interface and Level only Auto Largest Fixed Value Ifc Lvl Thresh Value Interface and Level only 0 to 100 echo strength units EoP Thresh Mode Auto Largest Fixed Value EoP Thresh Value 0 to 100 echo strength units ENDofPROBE ANALYSIS EoP Polarity Positive Negative EoP Analysis not used with...

Страница 43: ...y Fid Threshold Value SZ Hysteresis Safe Zone Hysteresis not used when Safe Zone Alarm is None 0 to 100 feet 0 to 30 m PROBE TARGET Compensation Auto Probe Target Mode Off Run Calibrate Targ Calib Ticks Target Ticks Elec Temp Offset Ifc Boundary Offset NAP Value Factory Reset FACTORY CALIB Factory password required Window Fiducial Ticks Conversion Factor Scale Offset 4 5 Model 706 Configuration Me...

Страница 44: ...M PACTware PC Program The ECLIPSE Model 706 offers the ability to perform more advanced diagnostics such as Trending and Echo Curve analysis using a PACTware DTM This is a powerful troubleshooting tool that can aid in the resolution of any diagnostic indicators that may appear 5 1 Diagnostic Parameters As mentioned above the ECLIPSE Model 706 measure ment engine runs through a series of self tests...

Страница 45: ...aus tive list of Diagnostic Indicators which follow the NAMUR NE 107 guidelines NAMUR is an international user association of automation technology in process industries whose goal is to promote the interest of the process industry by pooling experiences among its member companies In doing so this group promotes international standards for devices systems and technologies The objective of NAMUR NE...

Страница 46: ...categories Failure Function Check Out of Specification and Maintenance Required The FOUNDATION fieldbus version of the Model 706 trans mitter was implemented according to the Field Diagnostics Profile which is consistent with the objectives of NE 107 In the FOUNDATION fieldbus version diagnostic indicators can be mapped to multiple categories an example is shown in the diagram at left In this exam...

Страница 47: ...l 706 diagnostic indicators showing their priority explanations and recommended remedies Priority 1 is highest priority Priority indicator name default Category Explanation Remedy Context Sensitive Help 1 Software Error Failure Unrecoverable error occurred in stored program Contact MAGNETROL Technical Support 2 RAM Error Failure RAM read write memory failing 3 ADC Error Failure Analog to digital c...

Страница 48: ...nsitivity View Echo Curve 15 EoP Below ProbeEnd Failure End of Probe appears beyond Probe Length Check settings Probe Length Dielectric Range Sensitivity View Echo Curve 16 Safety Zone Alarm Failure Risk of echo loss if liquid rises above Blocking Distance Ensure that liquid cannot reach Blocking Distance 17 High Volume Alarm Failure Volume calculated from Level reading exceeds capacity of vessel ...

Страница 49: ...7 OK Reserved for future use 31 Inferred Level Out of Spec Distance measurement calculated indirectly from probe elongation Level reading is only approximate Verify Level reading If incorrect compare Dielectric Range against EoP Dielectric reading 32 Totalizer Data Lost Out of Spec Non volatile Totalizer Data storage failing Contact MAGNETROL Technical Support 33 No Probe Target Out of Spec Not ac...

Страница 50: ...ame explanation pairs exceeds the available space a appears in the rightmost column of the last line indicating more text below In this situation the DOWN key scrolls the text up Similarly while text exists above the upper line of the text field a appears in the rightmost column of the top text line In this situation the UP key scrolls the text down Otherwise the DOWN and UP keys are inoperative I...

Страница 51: ...lowing table assigns the proposed values of these characteristics in order of decreasing priority for each of the diagnostic conditions and or device configurations NOTES 1 Only the highest priority status will be indicated for a given process variable 2 If a process variable is not listed for a given diagnostic condition and or device configuration the status of that process variable is not affec...

Страница 52: ...limited Inferred Level Echo Strength Ifc Level Upper Thickness Ifc Echo Strength Probe Buildup Bad Device Failure Constant limited Totalizer Data Lost NR Totalizer R Totalizer Bad Config Error Not limited Default Parameters All PVs Bad Config Error Not limited EoP Above ProbeEnd All PVs except Elec Temperature Bad Config Error Not limited Buildup Detection disabled Probe Buildup Bad Config Error C...

Страница 53: ... Specific Constant limited TB Config Changed All PVs Good Non Specific Not limited Ramp Interval Error All PVs Good Non Specific Not limited High Elec Temp All PVs Good Non Specific Not limited Low Elec Temp All PVs Good Non Specific Not limited Calibration Req d All PVs Good Non Specific Not limited Echo Reject Invalid All PVs Good Non Specific Not limited No Probe Target All PVs Good Non Specifi...

Страница 54: ...eld is to be hard grounded only at one point close to the DCS In addition the cable shield can be capacitively grounded in multiple places to improve EMC protection Ensure all devices are on the live list and the schedule has been downloaded Ensure that the Resource Block then the Transducer Block and lastly the Function Block s are in Auto mode rather than Out of Service OOS If all of these requi...

Страница 55: ... ia nA ia Ga IIC T4 Ga Gc Ta 15ºC to 70ºC IP67 IEC IECEx FMG 14 00018X Ex ia nA ia Ga IIC T4 Ga Gc Ta 15ºC to 70ºC IP67 Intrinsically Safe US Canada Class I II III Div 1 Group A B C D E F G T4 Class I Zone 0 AEx ia IIC T4 Ga Class I Zone 0 Ex ia IIC T4 Ga Ta 40ºC to 70ºC Type 4X IP67 ATEX FM14ATEX0041X II 1 G Ex ia IIC T4 Ga Ta 40ºC to 70ºC IP67 IEC IECEx FMG 14 0018X Ex ia IIC T4 Ga Ta 40ºC to 70...

Страница 56: ... fieldbus circuit remains passive The cable used to interconnect the devices needs to have the parameters in the following range Loop resistance R 15 150 km Inductance per unit length L 0 4 1mH km Capacitance per unit length C 80 200nF km C C line line 0 5 C line screen if both lines are floating or C C line line C line screen if screen is connected to one line Length of splice 1m T box must only ...

Страница 57: ...foot 1 meter remote 2 No Digital Display or Keypad 12 foot 3 6 meter remote A Digital Display and Keypad Integral B Digital Display and Keypad 3 foot 1 meter remote C Digital Display and Keypad 12 foot 3 6 meter remote 8 CLASSIFICATION 0 General Purpose Weatherproof IP 67 1 Intrinsically Safe FM CSA CL 1 Div 1 Grps A B C D 3 Explosion proof FM CSA CL 1 Div 1 Grps B C D A Intrinsically Safe ATEX IE...

Страница 58: ...7 3 1500 ANSI RF 58 3 2500 ANSI RF 5K 3 600 ANSI RTJ 5L 3 900 ANSI RTJ 4 1 2 NPT Thread 5M 3 1500 ANSI RTJ 5N 3 2500 ANSI RTJ 6 3 4 150 ANSI RF 6 4 4 300 ANSI RF 6 5 4 600 ANSI RF 6 6 4 900 ANSI RF 6 7 4 1500 ANSI RF 6 8 4 2500 ANSI RF 6K 4 600 ANSI RTJ 6L 4 900 ANSI RTJ 6M 4 1500 ANSI RTJ 6N 4 2500 ANSI RTJ EN Flanges D A DN 50 PN 16 EN 1092 1 TYPE A D B DN 50 PN 25 40 EN 1092 1 TYPE A D D DN 50 ...

Страница 59: ... 1 4 2 PEEK HT Available only with 3rd digit D 650 F 345 C εr 1 4 3 Ceramic High Temp 800 F 425 C Available only with 3rd digit D εr 2 0 4 Celazole 800 F 425 C Available only with 3rd digit D εr 1 4 5 None with metal shorting rod εr 1 4 Future 10 O RING MATERIALS SEAL OPTIONS 0 Viton GFLT Available only with 3rd digit T 2 Kalrez 4079 Available only with 3rd digit T 8 Aegis PF 128 NACE Available on...

Страница 60: ... 50 PN 250 EN 1092 1 TYPE B2 D H DN 50 PN 320 EN 1092 1 TYPE B2 D J DN 50 PN 400 EN 1092 1 TYPE B2 E A DN 80 PN 16 EN 1092 1 TYPE A E B DN 80 PN 25 40 EN 1092 1 TYPE A E D DN 80 PN 63 EN 1092 1 TYPE B2 E E DN 80 PN 100 EN 1092 1 TYPE B2 E F DN 80 PN 160 EN 1092 1 TYPE B2 E G DN 80 PN 250 EN 1092 1 TYPE B2 E H DN 80 PN 320 EN 1092 1 TYPE B2 E J DN 80 PN 400 EN 1092 1 TYPE B2 F A DN 100 PN 16 EN 109...

Страница 61: ...y C C Monel Not available with 3rd Digit S R 316 SS 316L SS with Carbon Steel Flange S Hastelloy C with Carbon Steel Flange T Monel with Carbon Steel Flange Not available with 3rd Digit S 9 SPACER MATERIAL 1 TFE 400 F 200 C Only available with 3rd digit P or T εr 1 4 2 PEEK HT Only available with 3rd digit D 650 F 345 C or S 575 F 300 C εr 1 4 3 Ceramic Temp 650 F 345 C Only available with 3rd dig...

Страница 62: ...92 1 TYPE A D B DN 50 PN 25 40 EN 1092 1 TYPE A D D DN 50 PN 63 EN 1092 1 TYPE B2 D E DN 50 PN 100 EN 1092 1 TYPE B2 D F DN 50 PN 160 EN 1092 1 TYPE B2 D G DN 50 PN 250 EN 1092 1 TYPE B2 D H DN 50 PN 320 EN 1092 1 TYPE B2 D J DN 50 PN 400 EN 1092 1 TYPE B2 E A DN 80 PN 16 EN 1092 1 TYPE A E B DN 80 PN 25 40 EN 1092 1 TYPE A E D DN 80 PN 63 EN 1092 1 TYPE B2 E E DN 80 PN 100 EN 1092 1 TYPE B2 E F D...

Страница 63: ...able with 3rd digit J or L A Kalrez 6375 Not available with 3rd digit J or L D None Glass Ceramic Alloy Dual Seal Design with annuncia tor fitting Not available with 3rd digit G N None Glass Ceramic Alloy Not available with 3rd digit G A 316 SS 316L SS B Hastelloy C C Monel R 316 SS 316L SS with Carbon Steel Flange S Hastelloy C with Carbon Steel Flange T Monel with Carbon Steel Flange 11 PROBE SI...

Страница 64: ... PN 160 EN 1092 1 TYPE B2 D G DN 50 PN 250 EN 1092 1 TYPE B2 D H DN 50 PN 320 EN 1092 1 TYPE B2 D J DN 50 PN 400 EN 1092 1 TYPE B2 E A DN 80 PN 16 EN 1092 1 TYPE A E B DN 80 PN 25 40 EN 1092 1 TYPE A E D DN 80 PN 63 EN 1092 1 TYPE B2 E E DN 80 PN 100 EN 1092 1 TYPE B2 E F DN 80 PN 160 EN 1092 1 TYPE B2 E G DN 80 PN 250 EN 1092 1 TYPE B2 E H DN 80 PN 320 EN 1092 1 TYPE B2 E J DN 80 PN 400 EN 1092 1...

Страница 65: ... F Faced Flange PFA coated wetted surfaces Only available with Digit 3rd digit F P PFA coated rod Only available with Digit 3rd digit F R 316 SS 316L SS with Carbon Steel Flange S Hastelloy C with Carbon Steel Flange T Monel with Carbon Steel Flange 9 SPACER MATERIAL 0 None Not available with 3rd Digit N 2 PEEK HT 650 F 345 C Only available with 3rd digit N 3 Ceramic High Temp 800 F 425 C Only ava...

Страница 66: ... Future ANSI Flanges 4 3 2 150 ANSI RF 4 4 2 300 ANSI RF 4 5 2 600 ANSI RF 5 3 3 150 ANSI RF 5 4 3 300 ANSI RF 5 5 3 600 ANSI RF 6 3 4 150 ANSI RF 6 4 4 300 ANSI RF 6 5 4 600 ANSI RF EN Flanges D A DN 50 PN 16 EN 1092 1 TYPE A D B DN 50 PN 25 40 EN 1092 1 TYPE A D D DN 50 PN 63 EN 1092 1 TYPE B2 D E DN 50 PN 100 EN 1092 1 TYPE B2 E A DN 80 PN 16 EN 1092 1 TYPE A E B DN 80 PN 25 40 EN 1092 1 TYPE A...

Страница 67: ... model number 7 0 0 0 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 Non removable Probe Cable for use with 3rd digit 2 only 1 Removable Single piece Probe Cable for use with 3rd digit 1 only 9 WEIGHT MATERIAL 0 None 4 Celazole Available only with 3rd digit 6 8 MATERIAL OF CONSTRUCTION MFG NUT ROD INSULATION A 316 SS 316L SS F Faced Flange PFA Coated Wetted Surfaces Available only with 3rd digit 1 R 316 ...

Страница 68: ...4 300 lbs ANSI RF 6 5 4 600 lbs ANSI RF EN Flanges E A DN 80 PN 16 EN 1092 1 TYPE A E B DN 80 PN 25 40 EN 1092 1 TYPE A E D DN 80 PN 63 EN 1092 1 TYPE B2 E E DN 80 PN 100 EN 1092 1 TYPE B2 F A DN 100 PN 16 EN 1092 1 TYPE A F B DN 100 PN 25 40 EN 1092 1 TYPE A F D DN 100 PN 63 EN 1092 1 TYPE B2 F E DN 100 PN 100 EN 1092 1 TYPE B2 4 5 PROCESS CONNECTION SIZE TYPE consult factory for other process co...

Страница 69: ...rbon Steel Flange 9 SPACER MATERIAL 0 None 10 O RING MATERIALS SEAL OPTIONS 0 Viton GFLT 2 Kalrez 4079 Only available with 3rd digit 7 8 Aegis PF 128 NACE Only available with 3rd digit 7 A Kalrez 6375 Only available with 3rd digit 7 11 PROBE SIZE ELEMENT TYPE FLUSHING CONNECTION 3 Flexible Cable Probe 12 SPECIAL OPTIONS 0 None 13 14 15 INSERTION LENGTH X X X feet 003 100 meters 001 030 unit of mea...

Страница 70: ...n 089 9114 001 7x1 Single Rod Flexible Probe Weight 089 9120 001 6 4 2 Recommended Spare Parts item description Part number Electronic module Display Module Z31 2850 001 Potted Bezel Assembly Z31 2849 002 Terminal board General Purpose GP Intrinsically Safe IS Explosion Proof XP Z30 9166 001 S E G M E N T E D P R O B E O P T I O N S 1 2 t h D I G I T O F M O D E L N U M B E R Probe Model one Segme...

Страница 71: ...el Parameters Screen Every parameter in your radar transmitter can be monitored and modified remotely with a few clicks of the mouse From units of measure to settings for dielectric each parameter can be viewed or changed to suit application conditions Parameters can be developed offline or transferred between transmitters Trending Screen The ability to trend data over a period of time allows insi...

Страница 72: ...LEVEL_UNIT Level Unit 16 DISTANCE Distance 17 DISTANCE_UNIT Distance Unit 18 PROBE_MODEL Probe Model 19 PROBE_COATING Probe Coating 20 PROBE_MOUNT Probe Mount 21 PROBE_LENGTH Probe Length 22 PROBE_LEVEL_OFFSET Level Offset 23 DIELECTRIC_RANGE Dielectric Range 24 SENSITIVITY Sensitivity 25 BLOCKING_DISTANCE Blocking Distance 26 SAFETY_ZONE_MODE Safety Zone Mode 27 SAFETY_ZONE_HEIGHT Safety Zone Hei...

Страница 73: ...POLARITY EoP Polarity 50 EOP_DIELECTRIC EoP Dielectric 51 COMPENSATION_MODE Compensation Mode 52 VAPOR_DIELECTRIC Vapor Dielectric 53 HF_CABLE_LENGTH HF Cable Length 54 BUILDUP_DETECTION Buildup Detection 55 PARAMETER_RESET Parameter Reset 56 FIDUCIAL_TICKS Fiducial Ticks 57 FIDUCIAL_STRENGTH Fiducial Strength 58 LEVEL_TICKS Level Ticks 59 ECHO_STRENGTH Echo Strength 60 INTERFACE_TICKS Interface T...

Страница 74: ...E_TARGET_MODE Probe Target Mode 90 TARGET_CALIB_TICKS Target Calib Ticks 91 WINDOW_GWR Window 92 CONVERSION_FACTOR Conversion Factor 93 SCALE_OFFSET Scale Offset 94 M7YK_SCALE_OFFSET 7XK Scale Offset 95 FACTORY_PARAMETER_1 Factory Parameter 1 96 FACTORY_PARAMETER_2 Factory Parameter 2 97 FACTORY_PARAMETER_3 Factory Parameter 3 98 FACTORY_PARAMETER_4 Factory Parameter 4 99 MAGNETROL_SERIAL_NUMBER M...

Страница 75: ... Time 126 HIST_ENTRY1 Event History 1 127 HIST_ENTRY2 Event History 2 128 HIST_ENTRY3 Event History 3 129 HIST_ENTRY4 Event History 4 130 HIST_ENTRY5 Event History 5 131 HIST_ENTRY6 Event History 6 132 HIST_ENTRY7 Event History 7 133 HIST_ENTRY8 Event History 8 134 HIST_ENTRY9 Event History 9 135 HIST_ENTRY10 Event History 10 136 RESET_HISTORY Reset History 137 ECHO_HIST_TRIGGER_MODE Echo Hist Tri...

Страница 76: ... 161 DATA_LOG_RECORDS Log Data 162 PD_TAG_APPL_IMAGE PD Tag Volume transducer Block table Item Parameter Name Parameter Label 0 BLOCK_STRUCTURE BLOCK STRUCT 1 ST_REV Static Revision 2 TAG_DESC Tag Description 3 STRATEGY Strategy 4 ALERT_KEY Alert Key 5 MODE_BLK Block Mode 6 BLOCK_ERR Block Error 7 UPDATE_EVT Update Event 8 BLOCK_ALM Block Alarm 9 TRANSDUCER_DIRECTORY Transducer Directory 10 TRANSD...

Страница 77: ...e Pt 10 37 VOLUME_TABLE_PT_11 Volume Table Pt 11 38 VOLUME_TABLE_PT_12 Volume Table Pt 12 39 VOLUME_TABLE_PT_13 Volume Table Pt 13 40 VOLUME_TABLE_PT_14 Volume Table Pt 14 41 VOLUME_TABLE_PT_15 Volume Table Pt 15 42 VOLUME_TABLE_PT_16 Volume Table Pt 16 43 VOLUME_TABLE_PT_17 Volume Table Pt 17 44 VOLUME_TABLE_PT_18 Volume Table Pt 18 45 VOLUME_TABLE_PT_19 Volume Table Pt 19 46 VOLUME_TABLE_PT_20 V...

Страница 78: ...ameter Label 0 BLOCK_STRUCTURE BLOCK STRUCT 1 ST_REV Static Revision 2 TAG_DESC Tag Description 3 STRATEGY Strategy 4 ALERT_KEY Alert Key 5 MODE_BLK Block Mode 6 BLOCK_ERR Block Error 7 UPDATE_EVT Update Event 8 BLOCK_ALM Block alarm 9 TRANSDUCER_DIRECTORY Transducer Directory 10 TRANSDUCER_TYPE Transducer Type 11 XD_ERROR Transducer Error 12 COLLECTION_DIRECTORY Collection Directory 13 MEAS_TYPE ...

Страница 79: ...Generic Eqn K Factor 40 GENERIC_EQN_L_FACTOR Generic Eqn L Factor 41 GENERIC_EQN_C_FACTOR Generic Eqn C Factor 42 GENERIC_EQN_N_FACTOR Generic Eqn n Factor 43 FLOW_TABLE_TYPE Flow Table Type 44 FLOW_TABLE_LENGTH Flow Table Length 45 FLOW_TABLE_PT_01 Flow Table Pt 01 46 FLOW_TABLE_PT_02 Flow Table Pt 02 47 FLOW_TABLE_PT_03 Flow Table Pt 03 48 FLOW_TABLE_PT_04 Flow Table Pt 04 49 FLOW_TABLE_PT_05 Fl...

Страница 80: ... Pt 25 70 FLOW_TABLE_PT_26 Flow Table Pt 26 71 FLOW_TABLE_PT_27 Flow Table Pt 27 72 FLOW_TABLE_PT_28 Flow Table Pt 28 73 FLOW_TABLE_PT_29 Flow Table Pt 29 74 FLOW_TABLE_PT_30 Flow Table Pt 30 75 ENTER_PASSWORD Enter Password 76 PRESENT_STATUS Present Status 77 STATUS_INDICATORS_1 Status Indicators 78 STATUS_INDICATORS _2 Status Indicators 79 STATUS_INDICATORS _3 Status Indicators 80 STATUS_INDICAT...

Страница 81: ...81 57 646 ECLIPSE Guided Wave Radar Transmitter FOUNDATION fieldbus NOTES ...

Страница 82: ...82 57 646 ECLIPSE Guided Wave Radar Transmitter FOUNDATION fieldbus NOTES ...

Страница 83: ...83 57 646 ECLIPSE Guided Wave Radar Transmitter FOUNDATION fieldbus NOTES ...

Страница 84: ...e basis of the applicability of our warranty No claims for misapplication labor direct or consequen tial damage will be allowed Return Material Procedure So that we may efficiently process any materials that are returned it is essential that a Return Material Authorization RMA number be obtained from the factory prior to the material s return This is available through Magnetrol local representativ...