33
Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
Post Purge
Status
For purge & modulation models: 15 second post purge is started on
burner shutdown.
Program Switch Error
XX:XX:XX Lockout
Lockout
DIP switch improperly set or changed during cycle.
Purge to High Fire
Status
For modulation models only: Modulating motor is sent to high fire.
Purge to Low Fire
Status
For modulation models only: Modulating motor is sent to low fire.
Relay Fail
XX:XX:XX Lockout
Lockout
Internal relay(s) fail initial check. Check ratings. If lockout still occurs
after overload is eliminated, replace control.
Safe Start OK
Status
Control has completed internal safe-start check.
Unsafe Short
Status
For purge & modulation models: Combustion air switch is closed before
start-up or after shutdown; control holds start-up until switch reopens; if
interlocks close before switch opens, alarm is energized.
Unsafe Air Short
XX:XX:XX Lockout
Lockout
For purge & modulation models: Same conditions as above, except the
interlocks close before the switch reopens, causing a lockout and the
alarm being energized.
Unsafe Flame ON
Hold
Flame signal - actual, induced, or runaway scanner - is detected before
start-up or after shutdown. The fan is energized. If the cause is corrected
within 30 seconds, as in afterburn, the control will turn off the fan and
continue the sequence.
Unsafe Flame ON
XX:XX:XX Lockout
Lockout
Same conditions as above, except the cause has not been corrected
within 30 seconds, refansulting in a lockout and the alarm being
energized.
Unsafe Flame Purge
Hold
For purge & modulation models: Flame signal - actual, induced, or
runaway scanner - is detected during the selected purge time period.
The fan is energized. If the cause is corrected within 30 seconds, as in
afterburn, the control will turn off the and continue the sequence.
Unsafe Flame Purge
XX:XX:XX Lockout
Lockout
For purge & modulation models: Same conditions as above, except the
cause has not been corrected within 30 seconds, resulting in a lockout
and the alarm being energized.
V-Internal Fault
XX:XX:XX Lockout
Lockout
Internal control failure; replace controller.
Watchdog Fail
XX:XX:XX Lockout
Lockout
Internal control failure; replace controller.
XXXXXXX
XXXXXTESTXX
Status
In combination with other messages, shows the control is in the
minimum pilot test mode.
Message
Type
Explanation