background image

7

Eclipse Extern-A-Therm Recuperators, Design Guide 540, 3/9/2009

In addition when using the recuperators on aluminum
melting or holding furnaces, the exhaust temperature
must be diluted to less than 1300°F (704°C). This will
ensure that any aluminum in the exhaust will condense
out before entering the recuperator. Aluminum
condensing on the recuperator tubes will cause damage.
When in doubt consult Eclipse.

Ŷ

  Failure to observe these conditions can destroy

the recuperator and will void the warranty.

Determine the Size of Recuperator Required

It is assumed that the net BTU requirement is known. The
table below is an approximate guide for the efficiency with
an Extern-A-Therm recuperator at various furnace
temperatures with 10% excess combustion air. This is
sufficiently accurate to determine the size of recuperator
to use; it should not be used to determine actual gas
usage.

Calculate the gross BTU requirement using this efficiency,
then check the Extern-A-Therm recuperator capacities in
the datasheet to determine the size of recuperator.

Example:

Net required 1.0 mm BTU/hr with furnace temperature of
1700°F. Using the table above, the efficiency = 67%.

Therefore, the gross input = 1.0mm BTU/hr ÷ 0.67 =
1.49mm BTU/hr. From the datasheets, a 1500 MA 
Extern-A-Therm with a capacity of 0.4mm BTU/hr to
1.6mm BTU/hr must be used. If a higher preheated air
temperature is required the 2500 MA should be used.

Dilution Air

If the furnace temperature is above 2100°F dilution air
must be introduced to cool the exhaust gases to 2100°F
before they enter the recuperator. 

As a guide, the following chart can be used to determine
the amount of dilution air required.

Number of Extern-A-Therm Recuperators

It is recommended that one recuperator be used for each
zone of control. This has the advantage that the
combustion air flow is controlled on the cold side of the
recuperator. All the subsequent instructions and
descriptions are written with this assumption. If it is
required that a single Extern-A-Therm recuperator will
pre-heat the combustion air for multiple zones, consult
Eclipse.

Mounting the Recuperator

The Extern-A-Therm recuperators are designed for
vertical mounting with the recuperator tubes hanging
vertically down. If an alternative mounting arrangement is
required, contact Eclipse.

The recuperator and exhaust housings have sufficient
strength to be self supporting from the mounting flange,
and can support the eductor if fitted. Eclipse recommends
the use of flexible piping at the air inlet/outlet and
entrainment air connections to accommodate expansion
and contraction. See Figure 3.2 for a typical arrangement.

Do not add additional insulation to the outside of the
recuperator, as this will damage the unit.

Mounting the Eductor

The eductor can be mounted directly to the recuperator.
The outlet flange on the recuperator is of sufficient
strength to support the weight of the eductor; no additional
support is required for the eductor.

The standard eductor is designed for vertical mounting, if
horizontal mounting is required, consult Eclipse. No
additional exhaust ducting should be connected directly to
the eductor. 

There should be no restrictions at the eductor outlet; this
would affect the eductor performance. See Figure 3.3.
The outside of the eductor should not be insulated.

Furnace Temperature

°F (°C)

Efficiency with 

Extern-A-Therm Recuperator

1500 (815)

70%

1600 (817)

68.5%

1700 (926)

67%

1800 (982)

65.7%

1900 (1037)

64.4%

2000 (1093)

63%

2100 (1148)

60.6%

2200 (1204)

59.3%

2300 (1260)

58%

CAUTION

Furnace 

Temp 

°F (°C)

Burner Capacity BTU/hr (kW)

100,000

(29.3)

200,000

(58.6)

500,000

(146.5)

1,000,000

(293.1)

2,000,000

(586.1)

2200

(1204)

75

(2.1)

150

(4.3)

375

(10.6)

730

(20.7)

1,460

(41.3)

2300

(1260)

150

(4.2)

300

(8.5)

750

(21.2)

1,500

(42.4)

3,000

(84.9)

2400

(1315)

220

(6.2)

440

(12.4)

1,100

(31.1)

2,200

(62.3)

4,400

(124.6)

Table Values for 

Volume scfh (m

3

/hr) Cooling Air

Содержание 300 MA

Страница 1: ...Eclipse Extern A Therm Recuperators Models 300 MA 2500 MA Design Guide 540 3 9 2009...

Страница 2: ...duct whether due to breach of warranty negligence strict liability or otherwise is limited to the furnishing of replacement parts and Eclipse will not be liable for any other injury loss damage or exp...

Страница 3: ...5 Safety Warnings 5 Capabilities 5 Operator Training 5 Replacement Parts 5 System Design 6 Furnace Temperature Limits 6 Flue Gas Restrictions 6 Recuperator Sizing 7 Dilution Air 7 Number of Recuperat...

Страница 4: ...ease of installation and efficient use of existing pipe work The housings are internally insulated there is no need for additional external insulation Figure 1 1 Extern A Therm Recuperator Audience Th...

Страница 5: ...ribed herein without written advice from Eclipse Capabilities Adjustment maintenance and troubleshooting of the mechanical and the electrical parts of this system should be done by qualified personnel...

Страница 6: ...ld destroy the recuperator A high temperature protection limit switch must be fitted to ensure flue temperatures do not exceed 2100 F The recuperator must be positioned so that it will not be exposed...

Страница 7: ...w is controlled on the cold side of the recuperator All the subsequent instructions and descriptions are written with this assumption If it is required that a single Extern A Therm recuperator will pr...

Страница 8: ...lling the air and gas can be found in Design Guide 206 covering ThermJet Burners for Preheated Combustion Air Eductor Air Flow Eductors are designed to overcome the exhaust gas pressure drop through t...

Страница 9: ...ical Piping for Greater Furnace Pressure Control Eductor Air Combustion Air Dilution Air if Required Exhaust Gas Preheated Combustion Air to Burners Preheated Combustion Air to Burners Eductor Air Com...

Страница 10: ...5 x 10 3 millimeter mm inch in 3 94 x 10 2 MJ Nm BTU ft standard 2 491 x 10 2 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millime...

Страница 11: ...Offered By Power Equipment Company 2011 Williamsburg Road Richmond Virginia 23231 Phone 804 236 3800 Fax 804 236 3882 www peconet com...

Отзывы: