background image

Figure 5—View of Valve With Side Cover Removed

Instruction Manual 750  10/25/2004

Terminal Block

Lead Wires

Solenoid

Microswitch Bracket

Cast Solenoid Bracket

Three 10-32 Screws

7.0 Changing The Mounting Position in The Field

Warning:
Service must be done by a competent technician with prior experience and knowledge of safety shut-
off valves and safe maintenance procedures.

w

7.1

Turn off the gas supply to the valve and disconnect
the field installation elecrtical wiring before working
on the valve.  Conduit may also need to be removed
to allow proper orientation in the new mounting po-
sition.

7.2

If the valve is not mounted, clamp the body in a vise.

7.3

Connect a flexible temporary power source to termi-
nals 1 and 2.  Apply power and move the handle to
the open position.  Look at the visual indicator to
verify that the valve is open.  Do not remove power
during the following steps.

7.4

Loosen and remove the 8 hex-head bolts holding the
operator to the valve body.

7.5

Carefully lift the operator straight up until the stem
clears the body.

7.6

Inspect the gasket for any problem that may lead to
gas leakage.  If any problem is detected, stop and
contact Eclipse.

7.7

Rotate the operator to the desired position and care-
fully lower it straight into the valve body.

7.8

Replace and evenly tighten the 8 bolts to 50-60 lb-in
(approximately ½ turn after the hex-head is finger
tightened to contact the surface).

7.9

Interrupt the power source and observe that the
valve closes.  Reapply power and verify that the
valve opens properly.

7.10 

Disconnect the temporary power source.

7.11 

Restore the field connections and perform gas leak

 age tests before putting the system into service.

Содержание 200 LT Series

Страница 1: ... operator case These valves also include two SPDT micro switches that can be used for auxiliary circuits Two contacts are made when the valve opens and two are made when the valve is closed 1 0 Materials of Construction 1 1 Operator housing heat treated cast aluminum 1 2 Valve body cast aluminum or cast iron depending on model selected 1 3 Valve disc steel with Hycar synthetic rubber bonded to pro...

Страница 2: ... volts A C 3 0 Pressure Taps Position Indicators 2 6 LT valves are agency listed as follows UL listed for air natural gas LP gas hydrogen FM approved for natural LP manufactured gases CSA approved for natural LP mixed and manufac tured gases For wet or corrosive gases such as coke oven or di gester gas corrosion resistant trim must be installed at Eclipse Be sure your valve was ordered to suit you...

Страница 3: ...4 4 Wiring diagrams for the latching solenoid and microswitch es are located on the inside surface of the terminal block cover and also in Figure 4 4 5 The operator has two 1 2 threaded conduit con nections for field wiring Use wiring suitable for 75 C operation 4 6 For raintight applications wiring connections to the valve must be made with 90 close ell rigid conduit fittings The conduit should t...

Страница 4: ...and move the handle to the open position Look at the visual indicator to verify that the valve is open Do not remove power during the following steps 7 4 Loosen and remove the 8 hex head bolts holding the operator to the valve body 7 5 Carefully lift the operator straight up until the stem clears the body 7 6 Inspect the gasket for any problem that may lead to gas leakage If any problem is detecte...

Отзывы: