background image

4.0 Wiring

Figure 4—Wiring Details

Wiring Diagram

Terminal Block

5.0 Maintenance

5.1

Every six months, lubricate the lever with light mo-
tor oil as shown to the right.

5.2

Since the “LT” valve is a safety device, test it regu-
larly for proper functioning.  Interrupt electrical
power to simulate an unsafe condition.  

If the valve

does not close immediately, remove it from service
and replace.

4.1

Check valve nameplate to make certain electrical
characteristics correspond with electrical service be-
ing used.

4.2

All wiring connections should be made in accor-
dance with local or regional electric codes.

4.3

All internal wiring is connected at the factory to a
terminal block included in the built-in wiring
compartment of the valve (see figure 4).  Make all
field connections to this terminal block.  Strip the
wire 1/4"  to 3/8".  Insert into the terminal open-
ing and tighten the screws.  Check for loose
strands that may cause a short.

4.4

Wiring diagrams for the latching solenoid and
microswitch(es) are  located on the inside surface of
the terminal block cover, and also in Figure 4.

4.5

The operator has two 1/2" threaded conduit con-
nections for field wiring.  Use wiring suitable for 75°
C operation.

4.6

For raintight applications, wiring connections to the
valve must be made with 90° close ell rigid conduit
fittings.  The conduit should travel downwards
from the valve to cause water to flow away from the
valve.

Oil

Here

6.0

Replacement of Solenoid & Bracket Assembly 

(See Fig. 5 Page 4)

6.1

Remove main housing cover and gasket.

6.2

Remove the wiring box cover.  Disconnect solenoid
lead wires from the terminal block.

6.3

Remove the three 10-32 machine screws holding the
cast solenoid bracket and microswitch bracket to the
operator housing.  Remove both brackets.

6.4

Mount the new solenoid and bracket assembly in the
operator housing, replace the microswitch bracket,
replace the three 10-32 screws, reconnect lead wires,
and install main and side gaskets and covers.

3

Eclipse Locktite Manual Reset Gas Shut-Off Valves, Series 200 LT, Instruction Manual 750, 10/25/2004

Содержание 200 LT Series

Страница 1: ... operator case These valves also include two SPDT micro switches that can be used for auxiliary circuits Two contacts are made when the valve opens and two are made when the valve is closed 1 0 Materials of Construction 1 1 Operator housing heat treated cast aluminum 1 2 Valve body cast aluminum or cast iron depending on model selected 1 3 Valve disc steel with Hycar synthetic rubber bonded to pro...

Страница 2: ... volts A C 3 0 Pressure Taps Position Indicators 2 6 LT valves are agency listed as follows UL listed for air natural gas LP gas hydrogen FM approved for natural LP manufactured gases CSA approved for natural LP mixed and manufac tured gases For wet or corrosive gases such as coke oven or di gester gas corrosion resistant trim must be installed at Eclipse Be sure your valve was ordered to suit you...

Страница 3: ...4 4 Wiring diagrams for the latching solenoid and microswitch es are located on the inside surface of the terminal block cover and also in Figure 4 4 5 The operator has two 1 2 threaded conduit con nections for field wiring Use wiring suitable for 75 C operation 4 6 For raintight applications wiring connections to the valve must be made with 90 close ell rigid conduit fittings The conduit should t...

Страница 4: ...and move the handle to the open position Look at the visual indicator to verify that the valve is open Do not remove power during the following steps 7 4 Loosen and remove the 8 hex head bolts holding the operator to the valve body 7 5 Carefully lift the operator straight up until the stem clears the body 7 6 Inspect the gasket for any problem that may lead to gas leakage If any problem is detecte...

Отзывы: