KGL Operating Manual – VS 3010 BS
2018-07-02
/
136 178
SYSTEM ID: XXXXX
Enable of the EE valve 2 of the cascade controller.
Only visible when cascade controller is activated.
Menu 2-6-3 D2D Discharge gas defrosting
D2D ID: XXXXX
Com.disch.line XXX
Common discharge line solenoid valve 1 output
Drain htr. Z2 XXX
Drain heater Z2 cold rooms output
Defrost Z2 XXX
Manual defrost Z2/Z2 cases input
DisableDef Z2 XXX
Disable defrost Z2/Z2 cases input
HP cutout Z2 XXX
HP cutout input in Z1 suction line
Suct.line Z2 XXX
Solenoid valve 2.2/1 close suction line output
Discharge Z2 XXX
Discharge gas feed solenoid valve 3.2/1 output Z2/Z2 cases
Defrost Z2R XXX
Manual defrost input Z2 cold rooms
DisableDef Z2R XXX
Disable defrost input Z2 cold rooms
HP cutout Z2R XXX
HP cutout input in Z1 suction line Z2 cold rooms
Suct.line Z2R XXX
Solenoid valve 2.2/2 close suction line Z2 cold rooms output
Discharge Z2R XXX
Discharge gas feed solenoid valve 3.2/2 output Z2 cold rooms
Defrost Z1 XXX
Manual defrost Z1 input
DisableDef Z1 XXX
Disable defrost Z1 input
HP cutout Z1 XXX
HP cutout input in Z2 suction line
Suct.line Z1 XXX
Close suction line solenoid valve output Z1 cases
Discharge Z1 XXX
Discharge gas feed solenoid valve output Z1/Z1 cases
Menu 2 -7 Cascade controller
CASCADE ID: XXXXX
Temp. R4.1 XX°C.
Display of current refrigerant temperature / temperature sensor R4.1
Temp. R5.1 XX°C.
Display of current evaporator input temperature / temperature sensor R5.1
Temp. R6.1 XX°C.
Display of current evaporator output temperature / temperature sensor R6.1
to Z1 korr. XX°C
Display of current corrected evaporating temperature Z1
Act. tc Z2 XX°C
Display of current condensation temperature Z2
Setp. tc Z2 XX°C
Setpoint condensation temperature Z2
Act. SH XXK
display of current superheat Z1
Setp. SH XK
Setpoint superheat Z1
Valve V1 OFF
Display of current status enable expansion valve 1
Valve V2 OFF
Display of current status enable expansion valve 2
op.deg. D 0%
Display of current expansion valve opening degree as calculated by temperature controller
op.deg. SH 0%
Display of current expansion valve opening degree as calculated by superheat controller
op.deg. V 0%
Display of currently output expansion valve opening degree
9.1.4 Menu 3 Setpoints
SETPOINTS ID: XXXXX
1 System configuration
Continue to menu 3-1
2 Regulation
Continue to menu 3-2