KGL Operating Manual – VS 3010 BS
2018-07-02
/
118 178
7 VS 3010 BS operating modes
7.1 Manual / automatic emergency mode selection
Emergency operation of the compressor pack after a controller failure is possible using the manual / automatic
selection. The manual / automatic selection is realised at a relay level that is subordinate to the electronic
controller.
The manual / automatic selection of each compressor, gas cooler and fan is performed using the switches
S1…S8 located on the circuit board, see picture:
Only SIOX extension modules with manual control switch may be connected.
SIOX extension modules
!
without manual control switch are not authorised
The manual / automatic switching is available in the same way for the base module as well as for the
SIOX extension module.
The following switch positions are possible:
A: Automatic ON (default switch position)
If any switch is in the A position, the controller registers the logical AUTOMATIC OPERATION state:
The connected equipment is controlled
.
as the software envisages
O: Manual OFF
If any switch is in the 0 position, the controller registers the logical MANUAL OPERATION OFF state:
The connected equipment is
- even if the software envisages this
not controlled
, e.g. pump remains off continuously!
I: Manual ON
If any switch is in the I position, the controller registers the logical MANUAL OPERATION ON state:
The connected equipment is
- even if the software does not envisage this
always controlled
, e.g. pump remains on continuously!
The Manual OFF and Manual ON positions override the state desired by the software!