Firmware: V2.18 / V--
26.10.2022
86/119
9.5.2 Update der aktuellen Firmware
" (E) for the firmware update is available in the EDP at
edp.eckelmann.de/edp/lds/_RdC4ujAibE
and may have to be unpacked from the ZIP archive
use.
The firmware update is performed using a notebook (or PC) that is connected to the controller via the COM port
interface (RS232).
The following steps must be
strictly
performed and observed during the firmware update:
1. Strictly disconnect controller from the mains power supply (there
must
be absence of voltage) .
2. Set DIP switch S1 coding switches
6 and 7 to OFF
:
3. Connect controller (A) to flash cable (B) (connect both 4-pin plug connectors at the terminals 5/6/7/8 and
13/14//15/16).
4. Connect flash cable (B) to null modem cable (C).
5. Connect null modem cable (C) to the COM port (RS232) of the notebook (D)
6. In Windows Explorer, run the file
"GLT3010.exe"
by double clicking on it and select the used COM port on
the screen.
Содержание Compact GLT 3010
Страница 90: ...Firmware V2 18 V 26 10 2022 90 119 10 2 Connections for 230 V AC top Base module SIOX Extension Module ...
Страница 99: ...Firmware V2 18 V 26 10 2022 99 119 10 3 Connections for safety extra low voltage bottom ...
Страница 104: ...Firmware V2 18 V 26 10 2022 104 119 10 4 Connections for interfaces on the side Base module SIOX Extension Module ...