Firmware: V2.18 / V--
26.10.2022
95/119
10.2.2.1 Configuration of the digital inputs 230 V AC and 24 V AC/DC
Base module and SIOX extension modules
The digital inputs of the base module and those of the SIOX extension modules can be configured to 230 V AC
(
factory setting
) or to 24 V AC/DC using jumpers.
Wiring of the digital inputs using the example of a SIOX extension module with switches
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
BEFORE
connecting and disconnecting, it must be ensured that
no voltage
is present at all
connections of the controller.
Configuration of the jumpers:
Always carry out the work in a de-energised state and with the
connectors at the digital inputs disconnected!
Wiring of the digital inputs:
If 230 V AC is connected to an input that has been configured for
24 V AC, this results in destruction of the control component!
Mixed operation of the voltage levels!
If digital inputs with low voltage (230 V AC)
and
safety extra-
low voltage (24 V AC/DC) are required on a SIOX module, they
must
be separated by a digital input
connected
to
PE
!Practical tip:
Use of 2 separate SIOX modules to handle only one voltage level per module.
Содержание Compact GLT 3010
Страница 90: ...Firmware V2 18 V 26 10 2022 90 119 10 2 Connections for 230 V AC top Base module SIOX Extension Module...
Страница 99: ...Firmware V2 18 V 26 10 2022 99 119 10 3 Connections for safety extra low voltage bottom...