Firmware V6.6.9
29.07.2020
27/147
Parameter
Function
Horn
For the connection of an external audible alarm transmitter (factory setting). The contact
always switches if the internal buzzer of the controller also sounds (buzzer signals an
alarm). If the internal buzzer falls silent, the contact also switches to the idle state; see
also chapter
.
AUX relay Prio X3..X9
The multifunctional AUX relay has the same functionality as the two alarm outputs
PRIO1 / PRIO2 in chapter
, except that any desired message
priority between X3,X4, …or X9 can be assigned to it. If an alarm with the priority X3,X4,
… or X9 is received from an E*LDS component, the AUX relay output is only activated if
the message priority corresponds with that configured here; see also chapter
Modem reset
For further information, see chapter
.
GLT modem switching
For automatic modem switching to the building control (GLT) controller, see E*LDS
booklet for wiring details.
5.5.3 Relay outputs for week timers
By using up to a maximum of 4 SIOX extension modules (see chapter
SIOX - connection to the controller
), the
number of relay outputs can be increased by another 32 (8 relay outputs for each SIOX module, see Menu
4-1-1). Depending on the configuration and programming, the number of relay outputs can be even further
increased by using a GLT / DDC controller.
Configuration
Week timers with up to 7 control times (see Menu 4-1-4) can be configured for each relay output. The control
times can be set accurate to the minute and on individual weekdays or weekday groups.
Control times
authorised time period
Weekday
Mon, Tue, Wed, Thu, Fri, Sat, Sun
0:00 - 23:59
Weekday
groups
Mon-Fri, Mon-Sat, Sat-Sun
Start earliest 0:00
End latest 23:59, but not until after start time
The following applies: start time < end time
Control times over a day change are
not
authorised:
Example:
Start 21:00
End 07:00!
Mon-Sun (1 week)
0:00 - 23:59
Control times over a day change are authorised:
Example:
Start 20:00
End 08:00
In addition to the switching output, a passing contact, either as an alternative or in addition, can be defined for
each relay output. The passing contacts switch on simultaneously with the switching output and switch off again
after a duration of approx. 5 seconds. For connection details, see chapter
.SIOX - Terminal assignment of the
.
If the week timer should go over a day change (e.g. 20:00 - 8:00), it is only possible with individual
days, e.g. Mon 20:00 - 23:59 and Tue 0:00 - 8:00 or with the Mon-Sun weekday group as 20:00 - 8:00!
Individual control times are also permitted to overlap:
1. Week timer Mon-Sun 20:00 - 08:00
2. Week timer Sun 00:00 - 23:59