Menu structure of AL 300
41
Version 3-1 05. Dezember 2019
Danger of failure of alarm messaging!
The priorities for system and first start must not be set to
0, otherwise critical alarm messages cannot be transmitted! Successful transmission of alarms from
E*LDS components is not assured in systems where CAN bus communication is severely disturbed
(frequent reports of CAN faults or actual CAN failure).
S
Screen 7-5 Alarm Inputs
This screen can be used to configure the two device-specific alarm inputs (AL.1 und AL.2). An individual alarm
text can be entered for each alarm input and the respective alarm priority and delay can be defined.
The first page shows the current alarm status:
OK
- Power on
WAITNG
- Signalling, delay running, xxx minutes left
ALARM
- Power off
Inactive!
- Input not activated
An activated input can be deactivated by the DELETE command. The other settings remain unchanged.
If the input has generated an alarm at the time this is done, the alarm is reported as sent. Use the cursor keys
(
↑
) and (
↓
)to alternate between the two pages.
SIGNAL/ALARM INP
Page 1 – Show status
Entry
Text
Message text
↑
,
↓
Inp: XXXX/k
XXXX:
Name of input (1 = AL.1 and
2 = AL.2)
k:
Channel No.
Prio p Status
Input priority p and current status:
-
OK
No signal
-
WAIT xm
Signal, ,
x minutes delay remaining
-
ALARM
Signal, alarm/message generated
Press the ENTER key to move to the second page (Screen 7-5-a). The input displayed can be configured. An
activated input can be deactivated by the DELETE command. If the input has generated an alarm at the time
this is done, the alarm is reported as sent.
S
Screen 7-5-a
SIGNAL/ALARM INP
Page 2 - Configuration
Entry
Default
Text
Freely editable message text (max. 19 characters)
Text, num
bers
----
Priority
p
Message/alarm input priority
↑
,
↓
(number
0..99)
2
Delay
255m
Message/alarm delay in minutes
↑
,
↓
(number
0 .. 255)
0
Idle Current
J
N.C. input (Y) / N.O. input (N)
↑
,
↓
(Y/N)
J
delete
Delete message/alarm input:
Displays prompt: Are your sure? No: ESC Yes:
↵
↵
, ESC
S
Screen 7-6 .. 7-9
It is only possible to call up these screens if a system centre or a
CI 3000 / CI 3100 Store Computer is present and active in the E*LDS system. Further information about
this menu item can be found in the operating manuals of the System Centre and the Store Computer.
Содержание AL 300 W
Страница 21: ...Function of AL 300 16 Version 3 1 05 Dezember 2019 Notice ...
Страница 31: ...Pin and Terminal Assignments of AL 300 26 Version 3 1 05 Dezember 2019 Notice ...
Страница 51: ...Decommissioning and disposal 46 Version 3 1 05 Dezember 2019 Notice ...
Страница 59: ...Specifications of AL 300 54 Version 3 1 05 Dezember 2019 Notice ...
Страница 61: ...Order numbers and accessories of AL 300 56 Version 3 1 05 Dezember 2019 Notice ...