30
MN300820 Rev B4
Configuration
(with Display…Continued)
Step
Four
STEP 4 - SETTING THE FILL-H (FILL-HEIGHT)
1. In TOP-LEVEL MENU mode, select
TANK
.
2. Select
FILL-H
.
3. Using the UP and DOWN buttons, set the Fill Height
(
FILL-H
) of the tank (max. level of liquid to the bottom of
the tank).
4. To enter the value, press and hold OK for 2 seconds and
release.
SAVED
will display.
5. Select
EXIT
to return to TOP-LEVEL MENU.
Note: The Fill-Height (FILL-H) setting determines the 20 mA current span. To reverse the current output with
4mA being at the top of the tank, use the REV MA function.
Note: To speed up the scrolling of the values on the display, hold down the OK button while holding down the
UP or DOWN buttons.