background image

Echoflex Installation Guide

Photo & CCT Sensors

EEP Select

The default EEP setting is configured to work with Echoflex controllers.
You can configure the sensor to be compatible with controllers that use
an alternate profile.

1. Press and hold the

[Teach]

button until the green LED is displayed.

Release the button to enter the menu and display the first item, the
blinking green LED.

2. Press and release the

[Teach]

button to cycle through the menu of

color LEDs and stop when the blue and red LEDs are both blinking.

3. Press and hold the

[Teach]

button until the LEDs stop blinking to

select EEP Select. The blue and green LEDs blink code displays the
current setting.

4. Press and release the

[Teach]

button to navigate the options.

Indication

Setting

1 blue and green blink

EEP A5-06-02 Light Sensor

Light: 0–1,020 lux (0–95 fc)

Supply voltage: 0–5.1 V

2 blue and green blinks

EEP A5-06-04 Curtain Wall Brightness Sensor
(default)

Light: 0–65,535 lux (0–6,090 fc)

Battery level: 0–100%

3 blue and green blinks

EEP D2-14-25 Light Sensor and CCT *

Light: 0–100,000 lux (0–9,290 fc)

CCT: 0–32,767 kelvin

4 blue and green blinks

General Profile*

Light: 0–100,000 lux (0–6,090 fc)

CCT: 0–10,000 kelvin

* TAP-41 model only

5. Press and hold the

[Teach]

button to make a selection.

Photo & CCT Sensors

Page 7 of 8

Echoflex

Содержание TAP-31

Страница 1: ...oor values or predefined color temperature values The sensor supports four equipment profile settings that monitor exterior light levels up to 100 000 lux 9 290 fc and a color temperature range of 2 0...

Страница 2: ...Ceiling Tile 1 Use your fingers to remove the sensor s cover flexing it gently to release the tabs that hold it in place If you have difficulty try inserting a small flatblade screwdriver under one of...

Страница 3: ...rn button on the controller to activate Link mode If necessary refer to the controller product documentation 3 Press the Teach button on the sensor once to send a link message An LED blinks to confirm...

Страница 4: ...6 64 seconds 10 minutes 100 9 3 32 seconds 320 seconds 100 9 3 16 seconds 160 seconds For the sensor to send an on change message it needs sufficient power Stored energy above 3 5 V or Ambient light l...

Страница 5: ...confirms a good installation location 1 Press and hold the Teach button until the green LED is displayed Release the button to enter the menu and display the first item the blinking green LED 2 Press...

Страница 6: ...o 80 dBm good Red 80 to 95 dBm poor move closer No LED No linked controllers detected The test repeats every five seconds and runs for 50 seconds To exit before the time out press and hold the Teach b...

Страница 7: ...utton until the LEDs stop blinking to select EEP Select The blue and green LEDs blink code displays the current setting 4 Press and release the Teach button to navigate the options Indication Setting...

Страница 8: ...ons Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipment in a resid...

Отзывы: