background image

5

5

1. To enter Light Level Test mode, press and hold the teach button until the 

green LED begins to blink (about 6 seconds - LEDs are located on right hand 

side of the solar panel).

2. Press and hold the teach button again until the green LED stops blinking, 

about 6 seconds. The green LED will start blinking faster in accordance to 

the light level it is detecting, see tables below.

At 510 Lux (50 fc) range ( default )

blinks lux

foot candles time to fully charge

discharge time

0

< 50

<5 below operating level

n/a

1

< 142

<14 48.0 hours

67.0 hours

2

< 234

<23 26.5 hours

82.5 hours

3

< 326

<33 18.0 hours

86.75 hours

4

< 418

<42 13.25 hours

88.75 hours

5

>418

>42 11.0 hours

90.0 hours

At 1024 Lux (100 fc) range (switch selectable)

blinks lux

foot candles time to fully charge

discharge time

0

< 50

<5 below operating level

n/a

1

< 244

<24 26.0 hours

82.5 hours

2

< 438

<44 12.5 hours

89.25 hours

3

< 632

<63 10.0 hours

90.75 hours

4

< 826

<83 9.5 hours

91.0 hours

5

> 826

>83 9.0 hours

91.25 hours

T

he time to fully charge is based on the storage capacitor charging from a non-

operational condition. Discharge time indicates how long a fully charged sensor 

will  operate  in  the  dark.  The  test  will  repeat  every  2  seconds  and  run  for  a 

duration of 100 seconds. You may quit the test at any time by pressing the teach 

button for 6 seconds. 

Range  Confirmation  Test:

  This  test  provides  visual  feedback  of  the  sensors 

signal strength by a linked receiver with range confirmation capability.

Note:

•  Range Confirmation only available with “F series” Echoflex Controllers.
•  The TAP must be at full charge and/or have the battery installed for Range 

Confirmation Tests energy requirements.

•  Only one receiver can be linked to the sensor for proper operation of the test.
•  Disable repeaters in range for proper test operation.

1. To enter Range Confirmation Test mode, press and hold the teach button 

until the green LED begins to blink (about 6 seconds).

2. A quick press and release of the button at this point will allow you to select 

between test modes. Pressing and releasing the test button scrolls through 

Содержание TAP-21C

Страница 1: ...k Ambient Photo sensor also referred to as the sensor in this guide is a wireless energy harvesting sensor that monitors light levels within interior spaces and transmits the value to lighting control...

Страница 2: ...2 Page Left Blank Intentionally...

Страница 3: ...3 Supply Voltage 0 5 1V linear n 0 255 Daylight Harvesting The sensor will repeatedly broadcast a telegram on a timer heart beat timer The time period adjusts automatically to the ambient light levels...

Страница 4: ...foot candles or 1024 lux 100 foot candles The factory default is 512 lux 3 Press the rear mounting plate back into position Installing or Replacing the Start Assist Battery The battery is not require...

Страница 5: ...rs 5 826 83 9 0 hours 91 25 hours The time to fully charge is based on the storage capacitor charging from a non operational condition Discharge time indicates how long a fully charged sensor will ope...

Страница 6: ...ng the test button for 6 seconds Commissioning Test Mode This mode accelerates the time period between transmissions of the current light level to every 10 seconds for a duration of 5 minutes regardle...

Страница 7: ...ers and receivers on the same wall Avoid locating transmitters and receivers where the telegrams must penetrate walls at acute angles This increases the material the telegram must pass through reducin...

Страница 8: ...se undesired operation IC RSS 210 315MHz and 902 MHz models only Contains IC 5713A STM300C or 5713A STM300U Construction Type Conformity Certificate 928 MHz model only TCM 410J complies with the Japan...

Отзывы: