background image

Echoflex Installation Guide

Ceiling Vacancy-Occupancy Sensor

Prepare for Installation

To ensure optimal function, consider the installation environment and the
following guidelines:

For indoor use only. Operating temperature -10°C to 45°C
(14°F to 113°F), 5%–92% relative humidity (non-condensing).

High density construction materials and large metal appliances or
fixtures in the space may disrupt wireless transmissions.

Install the sensor within range of linked receivers or controllers,
24 m (80 ft). Consider adding a repeater to extend reception range.

Ensure the lens model is suitable for the detection application. For
small office spaces (lens A models), locate the sensor so the PIR lens
has a line-of-sight to the desktop. See

Sensor Coverage on page 9

.

Avoid locating the sensor where it can easily sense movement
outside of the intended space, such as hallways or adjacent rooms. If
these conditions are unavoidable, use lens mask stickers to block off
specific areas. See

Lens Masking on page 5

.

Do not install within 2.5 m (8 ft) of an HVAC airflow duct or vent.

For the solar-powered RVS model, before linking the sensor expose it
to a good light source for at least two minutes at 65 lux
(6 footcandles). Install the RVS with one solar cell facing a light
fixture.

Supplies required to install (not provided):

Two #6 screws, double-sided tape, or Velcro

®

Installation

The sensor is optimized for 2.4–3 m (8–10 ft) ceiling heights. It can be
attached to a suspended ceiling or finished wallboard ceiling, to a
magnetic surface, or to other surfaces using flexible adhesive. Determine
the installation method and follow the instructions.

Note:

Consider linking the sensor while you have access and

before replacing the cover. See

Link to a Controller on page 5

.

Wire Staples to Ceiling Tile

1. Use your fingers to remove the cover, flexing it gently to release the

tabs that hold it in place. If you have difficulty, consider inserting a
small flatblade screwdriver under a release tab.

2. Mark the sensor mounting location on the ceiling tile.

Ceiling Vacancy-Occupancy Sensor

Page 2 of 12

Echoflex

Содержание RVS-A-xW Series

Страница 1: ...es The vacancy ceiling sensor RVS has two solar cells to harvest energy when the lights are ON while the occupancy ceiling sensor RCS is battery powered to support auto ON occupancy sensor application...

Страница 2: ...to block off specific areas See Lens Masking on page 5 Do not install within 2 5 m 8 ft of an HVAC airflow duct or vent For the solar powered RVS model before linking the sensor expose it to a good li...

Страница 3: ...uble sided Tape or Velcro 1 Cut two lengths of tape not provided to the appropriate size and adhere one side to the mounting plate and the other to the ceiling 2 Press the sensor firmly in place Sensi...

Страница 4: ...upancy Timer and the controller s Occupancy Timer When the space is vacant and all timers have expired only PIR detection or manual control can change the state to occupied if the sensor is configured...

Страница 5: ...fer to the controller product documentation 3 Press the Teach button on the RVS RCS once to send a message An LED blinks to confirm a successful transmission 4 Deactivate Link mode on the controller b...

Страница 6: ...ructions Light Level Test green LED Range Confirmation blue LED Walk Test red LED Sensor Setting red and blue LEDs LED Display green and red LEDs The menu times out after two minutes of inactivity Lig...

Страница 7: ...inked controllers detected The test repeats every five seconds and runs for 50 seconds To exit before the time out press and hold the Teach button Walk Test The Walk Test verifies the boundaries or li...

Страница 8: ...nks Occupancy Timer DT model only Note Echoflex dual tech sensors have a configurable Occupancy Timer that sends a vacancy message when expired If using another controller brand with a DT model you ma...

Страница 9: ...when the green and red LEDs are both blinking 3 Press and hold the Teach button until the LEDs stop blinking to select LED Display 4 Press the Teach button to toggle between the two states Red LED bli...

Страница 10: ...io communications Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipm...

Страница 11: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 11 of 12 Echoflex...

Страница 12: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 12 of 12 Echoflex...

Отзывы: