6

Test /Setting  Modes

The following tests and settings can be changed while in test mode: 

•  Senso

r Setting Mode including PIR or Audio Sensitivity, and Sensor 

Occupancy Timer

•  Walk-Test Mode

• 

LED indication selection

Sensor Setting Mode

This mode allows 

adjustment of the PIR Sensitivity, Audio Sensitivity and Sensor 

Occupancy Timer duration. The faceplate must be removed to allow access to 

the teach button.
NOTE: New settings do not take affect until you save and exit.

1. 

To ent

er sensor setting mode, press and hold the teach button until all the 

LEDs blink simultaneously (about 5 seconds).

2. 

A quick press of the button at this level will allow you to scroll between the 

test/setting modes. When the red and yellow LEDs are blinking, go to step 3. 

3. 

Press and hold the button again until the LEDs stop blinking to select this 

mode, about 5 seconds.

4. 

A quick press of the button at this level scrolls between:

Double Green - PIR Sensitivity

Double Amber - Audio Gain (DT model only)

Double Red - Occupancy Sensor Timer (DT model only)

5. Press and hold the teach button again for 5 seconds to select the desired 

sensor setting. The corresponding LED will blink according to the current 

setting. Press the button to scroll through the available settings.

P

IR Sensitivity

 - green LED  blinks indicate setting

1 blink = high (default)

2 blinks = medium

3 blinks = low

Audio Sensitivity

 - amber LED  blinks indicate setting (DT model only)

1 blink = automatic (default)

2 blinks = low sensitivity

3 blinks = disabled

NOTE: If the Disabled setting is selected for Audio Gain, this disables the 

audio input however the Sensor Occupancy Timer will remain active. 

Senso

r

 

Occupancy Timer

 - red LED  blinks indicate setting (DT model 

only)

1 blink = disabled

2 blinks = 5 minutes 

3 blinks = 10 minutes

4 blinks = 15 minutes

5 blinks = 20 minutes (default)

6 blinks = 25 

minutes

NOTE: If the Disabled setting is selected for the Sensor Occupancy  Timer, 

the audio will remain active the entire 60 minute duration of the Audio 

Содержание OWS

Страница 1: ...ically OFF with vacancy When used with Echoflex Solution s dimming lighting controllers the switch also provides manual dimming control of the lights Echoflex controlled receptacles can also be automated with the OWS so plug loads operate ON or OFF with the current occupancy state The OWS communicates occupancy state and switch actuation wirelessly to Echoflex controllers The OWS models include a ...

Страница 2: ...PIR or audio must be detected to keep the audio active The default value for this timer is 20 minutes and it is configurable to values of 5 10 15 20 25 minutes or disabled If the sensor occupancy timer expires the OWS will send out a vacancy signal and 40 seconds later the audio will be disabled The 40 seconds is grace time that allows an occupant to use sound to reset the sensor occupancy timer a...

Страница 3: ...es It is the movement of the infrared energy moving in and out of a zone that defines occupancy The PIR interface cannot detect motion through solid objects including items placed by a tenant such as file cabinets or bookshelves Use the dual tech model for spaces with visual obstacles between the sensor and areas of intended motion The mounting location of the sensor is important as this will dire...

Страница 4: ...ine power and ground Use wire nuts on all connections The orange antenna wire should be left in the antenna channel as shipped Do not cut or cap the antenna wire 4 Restore power to the circuit 5 Before installing the faceplate the OWS should be linked to a receiver if not done previously Refer to the section later in this guide on the linking process 6 Install the faceplate not included A non meta...

Страница 5: ...objects linked and can be checked to confirm the linking process completed successfully Consult the manufacturer s controller receiver install guide for more information Linking the Wireless Switch 1 Place the receiver into LEARN mode by pressing the Learn button on the receiver Consult the manufacturers directions if needed 2 Quickly click the top side of the switch rocker 3 times 3 Deactivate LE...

Страница 6: ... this level scrolls between Double Green PIR Sensitivity Double Amber Audio Gain DT model only Double Red Occupancy Sensor Timer DT model only 5 Press and hold the teach button again for 5 seconds to select the desired sensor setting The corresponding LED will blink according to the current setting Press the button to scroll through the available settings PIR Sensitivity green LED blinks indicate ...

Страница 7: ... During normal operation the red LED will blink when the sensor transmits status after detecting occupancy This operation allows the user to turn off the indicator LED The faceplate must be removed to allow access to the teach button NOTE New settings do not take affect until you save and exit 1 To enter LED indication mode press and hold the teach button until all the LEDs blink simultaneously ab...

Страница 8: ... 284 16 FCC and IC Certifications 902 MHz The enclosed device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions I this device may not cause harmful interference and ii this device must accept any interference received including interference that may cause undesired operation Contains FCC ID SZV TCM320U Contains IC 5713A TCM320U echoflex Powered by ETC Echo...

Отзывы: