Echoflex Installation Guide

ElahoAccess Interface

Electrical Requirements

The ElahoAccess Interface requires 24 VDC (Class 2) power, supplied by an
external 24 VDC power supply. Termination for this connected is provided on
a removable pluggable connector, accepting 26-14 AWG (0.4-2.5 mm

2

) wires,

typically a black and red wire pair.

Note:

NEC Class 2 product to be wired in accordance to NEC Article

725 and local jurisdiction requirements.

EchoConnect

The Interface connects to the EchoConnect station communication bus.
EchoConnect is a bidirectional protocol that uses one pair of wires (data + and
data -). Echoflex recommends using Belden 8471 (or approved equal) Class 2
wire. The total combined length of an EchoConnect wire run (using Belden
8471, or equal) may not exceed 1,640 feet (500 m).

Note:

All control wiring should be installed and terminated by a

qualified installer and should follow standard wiring installation practices.

Leave approximately 8" (20 cm) of wiring in the back box for connection
and to allow slack for future service needs.

Note:

Echoflex requires that all Elaho stations and devices be grounded

for ESD protection. Pull an additional 14 AWG (2.5 mm

2

) wire for

grounding when control wires are not installed in grounded metal conduit.

ElahoAccess Interface Installation Guide

Page 2 of 8

Echoflex Solutions, Inc.

Содержание ElahoAccess Interface

Страница 1: ...and devices Prepare for installation wall plate alignment bracket interface Included in shipment The ElahoAccess Interface ships with interface assembly decorator style wall plate 24 VDC power pigtail...

Страница 2: ...t uses one pair of wires data and data Echoflex recommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not exce...

Страница 3: ...ll national and local codes for electrical equipment Note NEC Class 2 product to be wired in accordance to NEC Article 725 and local jurisdiction requirements Install the back box plumb and square for...

Страница 4: ...res and the installed Belden 8471 control wires One WAGO should be used for the white wire pair data and one for the black wire pair data Open the terminal levers on the WAGO connector and insert the...

Страница 5: ...d when installing the Interface in a surface mounted box 1 Insert the Interface electronics and wiring into the back box To install multiple Elaho products multi gang insert the Interface electronics...

Страница 6: ...ate is secured to the Interface with magnets that are assembled to the wall plate 1 Align the top of the wall plate to the Interface and angle the bottom approximately 20 degrees 2 Hook the top of the...

Страница 7: ...tes uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee t...

Страница 8: ...Echoflex Installation Guide ElahoAccess Interface ElahoAccess Interface Installation Guide Page 8 of 8 Echoflex Solutions Inc...

Отзывы: