5-8 Network Cabling and System Performance
Table 5.6
Simplified Power Specifications Using Level 4/22AWG (0.65mm) Wire
Nominal
Worst
Case
Units
400 meter branch length,
Evenly distributed loading along a bus
application current:
25 mA
74
53
devices
50
mA
37 26
100
mA
18 13
400 meter branch length,
Lumped loading or otherwise distributed
application current:
25 mA
37
26
devices
50
mA
18 13
100
mA
9
6
Table 5.7
Simplified Power Specifications Using Category 5 Wire
Nominal
Worst
Case
Units
400 meter branch length,
Evenly distributed loading along a bus
application current:
25 mA
47
34
devices
50
mA
23 17
100
mA
12
8
400 meter branch length,
Lumped loading or otherwise distributed
application current:
25 mA
23
16
devices
50
mA
11
8
100
mA
6
4
Power Specifications for Extended Performance
Although more complex, this alternative power specification allows for extended power
performance. In addition, it features a separate derating for the average wire temperature.