i
.LON SmartServer Hardware Guide
3
b.
Open Internet Explorer 6 or later and enter the following URL: 192.168.1.222. Your
SmartServer home page opens.
c.
Click the
Login
button. A login dialog appears. Enter
ilon
for both the
User Name
and the
Password
and then click
OK
. The
i.LON SmartServer – Welcome
Web page opens.
d.
You can configure your SmartServer and begin using its embedded applications as described
in the
i.LON SmartServer User’s Guide
.
Mounting the SmartServer
!
Caution
The SmartServer is intended to be mounted inside a suitable, safety-agency approved
enclosure that is mounted in a restricted access area. High-voltage wiring must be
performed only by a qualified service person.
The SmartServer mounts to a 35mm x 7.5mm or 35mm x 15mm DIN rail. The rear of the SmartServer
enclosure contains a spring-loaded DIN rail lock, which securely grabs the DIN rail on which the
enclosure is mounted. To release the enclosure from the DIN rail, insert a flathead screwdriver into the
DIN rail locking tab and gently pull the tab downwards and away from the enclosure. The following
figure displays the location of the DIN rail-locking tab. All units are in millimeters.
The following figure displays the dimensions of the SmartServer and the space required for the various
connections. All units are in millimeters.