Automatic Transfer Switch - VERSO 200 - Attachment 1
designation
function
Possible values
Std settings
Type
Mains
3P+N, 3P, 2P+N, 1P+N
AUTOCONF
Unom
Voltage in Volts
440, 415, 400, 380, 240, 230, 220, 208
AUTOCONF
Fnom
Frequency in Hz
50Hz, 60Hz
AUTOCONF
(1)
_
U<%
Default min mains U threshold
Range of adjustment dependant on apparatus
15
(2)
_
U<%
Default min genset U threshold
Range of adjustment dependant on apparatus
15
(1)
_
U>%
Default max mains U threshold
Range of adjustment dependant on apparatus
10
(2)
_
U>%
Default max genset U threshold
Range of adjustment dependant on apparatus
10
(1)
_
Hz<%
Default min mains F threshold
Range of adjustment dependant on apparatus
5
(2)
_
Hz<%
Default min genset F threshold
Range of adjustment dependant on apparatus
5
(1)
_
Hz>%
Default max mains F threshold
Range of adjustment dependant on apparatus
5
(2)
_
Hz>%
Default max genset F threshold
Range of adjustment dependant on apparatus
5
ABC
Direction of phase rotation
ABC, ACB, OFF (no management)
ABC
(1)
_
V/V
Adjustment of mains voltage measuring
Voltage gain adjustment (1=0,1V) (e.g.: )
1000
(2)
_
V/V
Adjustment of genset voltage measuring
Voltage gain adjustment (1=0,1V) (e.g.:)
1000
Position
Management of returns positions
YES=management, NO=no management
YES
Bklight
LCD screen backlight
99
Contrast
LCD screen contrast
50
Modbus
Modbus card
YES=with Modbus, NO=without Modbus
NO
Prio EJP
Default priority to EJP (*STOR)
(France only)
YES=application, NO=no application
NO
(1)
_
OK?
Manual confirmation of return to mains
YES=confirmation required, NO=confirmation not required
NO
NO %
No management of U and F limits
OFF=operation with limits, ON=operation without limits
OFF
Hyst/U%
Hysteresis U value
between 0% and 3% (of voltage limit)
2
Hyst/F%
Hysteresis F value
between 0% and 2% (of frequency limit)
0
(1)
_
+/-
Measuring card adjustment
Adjustment of offset voltage of measuring card 5A07
100
List of parameters
A11
N°
function
Range of
adjustment
Standard
range
N°
function
Range of
adjustment
Std
settings
T00 Loss of source 1
0s to 180s
3
T26 Screen scrolling time
1s to 10s
5
T01 Return source 2
0s to 999s
5
T27 Automatic configuration
0s to 999s
3
T02 min U source 1
0s to 999s
5
T28 Min critical U source 1
0s to 999s
1
T03 max U source 1
0s to 999s
5
T29 Max critical U source 1
0s to 999s
1
T04 min U source 2
0s to 999s
5
T30 min critical U source 2
0s to 999s
5
T05 max U source 2
0s to 999s
5
T31 max critical U source 2
0s to 999s
5
T06 min F source 1
0s to 999s
5
T32 min critical F source 1
0s to 999s
1
T07 max F source 1
0s to 999s
5
T33 max critical F source 1
0s to 999s
1
T08 min F source 2
0s to 999s
5
T34 min critical F source 2
0s to 999s
5
T09 max F source 2
0s to 999s
5
T35 max critical F source 2
0s to 999s
5
T10 default command source 1
2s to 999s
5
T36 last fault source 1
0s/10 to 999s/10
5
T11 default command source 2
2s to 999s
5
T37 reserve
0s to 999s
1
T12 Source change over
0s/10 to 999s/10
10
T38 last fault source 2
0s/10 to 999s/10
5
T13 U stabilisation source 1
0s/10 to 999s/10
10
T39 reserve
0s to 999s
1
T14 U stabilisation source 2
0s/10 to 999s/10
30
T40 production demand
0s to 999s
10
T15 U setting source 1
0s/10 to 999s/10
5
T41 switch power supply
0s to 999s
3
T16 U setting source 2
0s/10 to 999s/10
5
T42 activate back-light
0s to 999s
15
T17 Genset cooling source 1
0s to 999s
60
T43 Default opening at source 1
0s to 999s
5
T18 Genset cooling source 2
0s to 999s
60
T44 Default opening at source 2
0s to 999s
5
T19 test
0s to 999s
600
T45 reserve
0s to 999s
3
T20 advance warning EJP (*STOR) 0min to 999min
20
T46 reserve
0s to 999s
3
T21 loss EJP (*STOR)
0s to 999s
600
T47 reserve
0s to 999s
3
T22 load shedding
0s to 999s
10
T48 reserve
0s to 999s
3
T23 non-start
0s to 999s
30
T49 reserve
0s to 999s
3
T24 return to home screen
0s to 999s
120
T25 Standby
0s to 999s
120
s=second min=minute s/10= tenth of a second U=voltage F=frequency
*STOR=
Short Term Operating Reserve
List of timers
A12