Information, reports, alarms and faults are displayed as coded messages.
On the first line only the following messages may be displayed:
(1) OK
source 1 operational
(2) OK
source 2 operational
(1) ???
source 1 detected but configuration incompatible
(2) ???
source 1 detected but configuration incompatible
(1) U<%
Under-voltage alarm or fault at source 1
(2) U<%
Under-voltage alarm or fault at source 2
(1) U>%
Over-voltage alarm or fault at source 1
(2) U>%
Over-voltage alarm or fault at source 2
(1) F<%
Under-frequency alarm or fault at source 1
(2) F<%
Under-frequency alarm or fault at source 2
(1) F>%
Over-frequency alarm or fault at source 1
(2) F>%
Over-frequency alarm or fault at source 2
(1) ACB
Phase rotation fault at source 1
(2) ACB
Phase rotation fault at source 2
On the third line only the following messages may be displayed:
(0) -> (1) =SOS
Failure to close at source 1
(0) -> (2) =SOS
Failure to close at source 2
(1) -> (0) =SOS
Failure to open at source 1
(2) -> (0) =SOS
Failure to open at source 2
(1) =SOS ACB
Phase sequence fault at source 1
(2) =SOS ACB
Phase sequence fault at source 2
(2) =SOS GEN START
Genset fail to start
note
: With regards to the messages mentioned in this table, the fourth line will display the message RESET =
OK meaning « Press OK » to reset the fault
On the third line only the following action messages may be displayed:
ATS = 0
Opening function at source 1 & 2
AUTOSET =OK
auto-configuration initialising
MODE EJP
EJP (STOR*) mode engaged
(France only)
|--AUTOSET--|
auto-configuration in progress
(flashing)
PROGRAM
Program in progress
(+ DEL “test” switched on)
On the third and fourth lines the following action messages may be displayed:
T00=003s
(1) -> (0)
Transfer Timer
(1) =OK CONFIRM ?
_____
CONFIRM=OK
Manual confirmation of return to
mains
T01=005s
(2) -> (1)
Return to mains timer
T19=600s
MODE TEST
Test mode ongoing
T17=060s
(1) <°C
Genset cooling timer
(source 1)
(not implemented)
T18=060s
(2) <°C
Genset cooling timer
(source 2)
T20=020min
Préavis EJP
Advance notice of EJP (STOR*) timer
*
Short Term Operating Reserve
T21=600min
Perte EJP
loss of EJP (STOR*) timer
*Short Term Operating Reserve
Pressing TEST will light up LED [8], start up the generating set and make the screen displayed below appear.
Two possible modes:
- test with load (TEST>0KW=OK), press OK to select this mode,
- test without load (TEST 0KW=EXIT), press
to select this mode.
The user will have a period of 30 seconds to make a selection.
If no action is taken by the user, ‘TEST without load’ mode is selected automatically.
Displays: Information, alarms, faults and statuses
13
TEST mode
14
1-
Press OK for access to various menus,
2-
Press OK to access
LAMPS TEST menu
,
3-
Press OK. All LED’s and entire screen will light up.
1-
Press OK,
2-
Press
until you reach
STATS
,
3-
Press OK to access
4-
Press
, to access
Lamps test
15
STATS menu
16
1-
Press OK,
2-
Press
until you reach
EVENTS
,
3-
Press OK,
4-
Press
or
, to access the time-stamped list
EVENTS menu
17