Operating instructions - SBU IO-Link
Page 38 of 50
Check the earthing of the SBU IO-Link .
Switch the SBU IO-Link on and carry out a test run. Make sure that when control pressure is
applied, the respective valve or quarter turn actuator is driven to the intended end position with the
corresponding control commands "CLOSED" and "OPEN".
F02
RGB LED View
The supplied SBU IO-Link has two RGB light
elements that light up in a configured color when the
end position "CLOSED" and "OPEN" is reached.
More details about the colors can be found on the
IODD interface description. The colors can be
changed or deactivated via IO-Link. The factory
setting for the end positions is "green" - CLOSED
and " yellow" - OPEN.