97
Typ EP 501
Auxiliary functions
24.2.5.
SPLTRNG –
Signal split range
Min. and max. values of the input signal as % for which the valve runs through the entire stroke range.
Factory setting:
Min = 0 %; Max = 100 %
Type.EP.501.C:
The
SPLTRNG
auxiliary function can only be selected when operating as a positioner.
P.CONTROL
= not activated.
Use this auxiliary function to limit the position set-point value range of the Device by specifying a minimum and a
maximum value.
As a result, it is possible to divide a utilised standard signal range (4 – 20 mA; 0 – 20 mA; 0 – 10 V or 0 – 5 V) into
several devices (without or with overlapping).
This allows several valves to be used
alternately
or in the case of overlapping set-point value ranges
simultane-
ously
as actuating element.
EXIT
*
OK
Enter
value
Enter
value
SPLTRNG
Min 0 %
Max 100 %
Input the minimum value of the
input signal as %.
Adjustment range: 0 – 75 %
Input the maximum value of the
input signal as %.
Adjustment range: 25 – 100 %
ENTER
INPUT
INPUT
* If the submenu is left by pressing the
ESC
key, the value remains unchanged.
Figure 52:
Operating structure SPLTRNG
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
EXIT
. During the save process, the save
symbol is indicated on the display.
Splitting.a.standard.signal.range.into.two.set-point.value.ranges
4
6
8
10 12 14 16 18 20
100
Valve stroke [%] (
POS
)
Set-point value [mA]
(
INP
)
Set-point value range
Positioner 1
Set-point value range
Positioner 2
Figure 53:
Graph - SPLTRNG
english