background image

Operating instructions

W3G910-GN46-21

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1

Direction of air flow "V"

2

Cable PVC AWG18, 5x crimped ferrules

4

Cable PVC AWG22, 3x crimped ferrules

Item no. 50602-5-9970 · ENU · Change 89187 · Approved 2016-04-16 · Page 4 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G910-GN46-21

Страница 1: ...herwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical...

Страница 2: ...the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devic...

Страница 3: ...r operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment w...

Страница 4: ...dimensions in mm 1 Direction of air flow V 2 Cable PVC AWG18 5x crimped ferrules 4 Cable PVC AWG22 3x crimped ferrules Item no 50602 5 9970 ENU Change 89187 Approved 2016 04 16 Page 4 11 ebm papst Mu...

Страница 5: ...motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 34 kg Fan size 910 mm Rotor surface Painted black Electronics housing material Die cast aluminum painte...

Страница 6: ...r switching off supply with multiple devices connected in parallel Electric shock risk of injury Ensure sufficient protection against accidental contact Before working on the electrical hookup short t...

Страница 7: ...yed tripping super resistant characteristic K 4 2 4 Locked rotor protection Due to the locked rotor protection the starting current LRA is equal to or less than the nominal current FLA 4 3 Connecting...

Страница 8: ...eak for failure 2 A max 250 VAC min 10 mA AC1 1 6 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 k SELV 2 11 10 VDC red Voltage o...

Страница 9: ...ion detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range...

Страница 10: ...t operates an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development st...

Страница 11: ...spose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 50602 5 9970 ENU Change 89187 Approved 2016 04...

Отзывы: