Approval

UL 1004-7 + 60730-1; CSA C22.2 No.
77 + CAN/CSA-E60730-1; EAC

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.5 Mounting data

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

Strength class of
screws

8.8

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.6 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+70 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

3.7 Accessories

3.7.1 AxiCool heating tape

A heating tape that can be integrated into the fan housing is available for
the AxiCool fans. To prevent ice formation, ebm-papst recommends the
use of a heating tape for all applications below 0°C. The heating tape
designed for the AxiCool fan housing is available from ebm-papst under
the following item number.

Size

Item no.

630 mm

00630-2-7680

During assembly, comply with the installation instructions included with
each ebm-papst heating tape. ebm-papst assumes no liability when
heating tapes from other manufacturers are used. Note the maximum
permitted temperature of +80 ± 5 °C for the heating tape to prevent
damage to the fan housing.

NOTE
The heating tape has only basic insulation.

→ The heating tape may only be used with a closed fan

housing cover to prevent heat losses and contact with live
parts.

3.7.2 AxiCool drip pan

A heated drip pan that reliably discharges any water emerging from the
outflow side is available for the AxiCool fans. ebm-papst recommends
the use of a drip pan in conjunction with the AxiCool heating tape. The
drip pan designed for the AxiCool fan housing is available from ebm-
papst under the following item number.

Size

Item no.

630 mm

41201-1-4050

Installation instructions are included with every ebm-papst drip pan and
must be heeded on assembly.

3.7.3 AxiCool terminal box

A terminal box kit for attachment to the fan housing is available for
AxiCool fans. This terminal box kit provides an ideal means of
connecting the electrical connections of the motor, heating tape and drip
pan. The terminal box kit to suit the AxiCool fan housing and motor is
available from ebm-papst under the following item number.

Motor/connection

Item no.

M3G084, M3G112 /EC

50025-1-7612

Installation instructions are included with every ebm-papst terminal box
kit and must be heeded on assembly.

3.8 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2 (industrial
environment)

EMC circuit feedback

According to EN 61000-3-2/3

EMC interference
emission

According to EN 61000-6-3 (household
environment)

Item no. 55303-5-9970 · ENU · Change 222314 · Approved 2021-02-01 · Page 7 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание W3G630-KL06-G2

Страница 1: ...install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be ass...

Страница 2: ...appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compl...

Страница 3: ...ctions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation...

Страница 4: ...m 1 Direction of air flow V 2 Cable PVC AWG18 5x crimped ferrules 3 Cable PVC AWG22 5x crimped ferrules 4 Mounting holes for FlowGrid Item no 55303 5 9970 ENU Change 222314 Approved 2021 02 01 Page 4...

Страница 5: ...ort struts only in X position as illustrated or rotor on bottom 2 For horizontal shaft installation position the cable exit must be at the bottom right Item no 55303 5 9970 ENU Change 222314 Approved...

Страница 6: ...asurement setup 3 4 Technical description Weight 14 kg Size 630 mm Motor size 84 Rotor surface Painted black Electronics housing material Die cast aluminum painted black Blade material Press fitted sh...

Страница 7: ...om ebm papst under the following item number Size Item no 630 mm 00630 2 7680 During assembly comply with the installation instructions included with each ebm papst heating tape ebm papst assumes no l...

Страница 8: ...ion concerned 4 2 Electrical connection DANGER Voltage on the device Electric shock Always connect a protective earth first Check the protective earth DANGER Faulty insulation Risk of fatal injury fro...

Страница 9: ...sulation of the alarm relay As the alarm relay only has basic insulation for TN TT systems or functional insulation for phase conductor grounded networks with respect to the supply voltage and not dou...

Страница 10: ...rating 250 VAC 2 A AC1 min 10 mA basic insulation on supply side and reinforced insulation on control interface side 2 8 0 10 V yellow Analog input set value SELV 0 10 V Ri 100 k adjustable curve 2 9...

Страница 11: ...and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequencies must be determined in the course of fan...

Страница 12: ...ocate and rectify cause of error release restart lockout if necessary Ambient temperature too high Reduce the ambient temperature Reset by reducing control input to 0 Impermissible point of operation...