Operating instructions
W3G630-KL06-G2
Translation of the original operating instructions
4.5 Connection diagram
Drawing preliminary!
No.
Conn.
Designation
Color
Function/assignment
1
1, 2
PE
green/
yellow
Protective earth
1
3
N
blue
Power supply, neutral conductor, 50/60 Hz
1
5
L
black
Power supply, phase, 50/60 Hz
1
6
NC
white 1
Status relay, floating status contact, break for failure, contact rating 250 VAC / 2 A (AC1) / min. 10
mA; basic insulation on supply side and reinforced insulation on control interface side
1
7
COM
white 2
Status relay, floating status contact, break for failure, contact rating 250 VAC / 2 A (AC1) / min. 10
mA; basic insulation on supply side and reinforced insulation on control interface side
2
8
0-10 V
yellow
Analog input (set value) SELV, 0-10 V, Ri = 100 kΩ, adjustable curve
2
9
Tacho
gray
Tach output: open collector, 1 pulse per revolution, Isink max = 10 mA, SELV
2
10
RSB
brown
RS485 interface for MODBUS, RSB; SELV
2
11
RSA
white
RS485 interface for MODBUS, RSA; SELV
2
12
GND
blue
Reference ground for control interface, SELV
2
13
+10 V
red
Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof power supply for
external devices (e.g. pot); SELV
Item no. 55303-5-9970 · ENU · Change 222314 · Approved 2021-02-01 · Page 10 / 13